| Technical data |
| Enclosure design | Front panel mounting |
| Output contacts | 1 C/O contact |
| Time function(s) | On-delay |
| Width | 96 mm |
| Type | EH 7616 |
| Variant |
| Contact equipping | 1 NC contact delayed, 1 NC contact undelayed, 1 NO contact delayed, 1 NO contact undelayed |
| Nominal voltage | DC 24 V |
| Time range | 0,2 s - 60 h |
The Dold time relay type EH7616.24 DC24V 0,2S-60H is a delayed-action industrial time relay for front panel mounting, used for time-controlled operation of electrical devices and system components. It enables the setting of delay times between the application of operating voltage and the activation of output contacts, allowing for example the consideration of motor start-up behavior or the sequential commissioning of machine parts. The device is part of the MINITIMER series and complies with standard EN 61812-1 for time relays.
Applications
This time relay is suitable for applications in industrial automation where precise time control is required. Typical uses include switching pumps, fans, heating systems, or controlling machine tools, where a delay between actuating a switch and initiating a function is necessary. The wide adjustment range from 0.2 seconds to 60 hours allows flexible use in various processes.
Functions and equipment in detail
The device features contact configuration with one delayed normally open contact, one immediate normally open contact, one delayed normally closed contact, and one immediate normally closed contact, equivalent to a changeover contact. The delayed contacts switch only after the set time has elapsed, while the immediate contacts switch instantly upon application of operating voltage. The time delay is adjusted via a continuously variable rotary switch on the front panel. Repeatability is ≤ ± 0.5 %, with a permissible deviation of ≤ ± 1 % in the range of 3 and 6 seconds. A time progress indicator with a red pointer on the scale shows the progress of the delay time.
Technology explained simply
The time control is purely mechanical, driven by a synchronous motor powered by the operating voltage connected at terminals A1-A2. The delay time is determined by the motor speed and the setting of the rotary switch. If the operating voltage at A1-A2 is interrupted, the timing sequence is reset. The version without additional control terminals B1-B2 switches immediately upon voltage application, while a version with B1-B2 starts the time delay only when voltage is applied at B1-B2. Frequency switching between 50 and 60 Hz is performed on the rear of the device via a ratchet adjustment using a screwdriver.
Compatibility and accessories
The time relay is designed for a nominal voltage of DC 24 V and can be used in control systems with corresponding voltage supply. It has a width of 96 mm and is designed for front panel mounting. The front face measures 96 x 96 mm. Devices in the MINITIMER series are available in various sizes and versions, with the EH 7616 variant having the largest width. An optional voltage-free version is available, which retains the elapsed time during voltage interruption.
Mounting and installation
The device is installed in a front panel with a minimum depth of 40 mm. Mounting is done by screwing to the panel. The connection terminals are clearly labeled: A1-A2 for operating voltage, B1-B2 optionally for control voltage, and contacts 15-16 (delayed normally open), 27-28 (delayed normally closed), 31-32 (immediate normally open), 43-44 (immediate normally closed). The delay time is adjusted via the rotary switch on the front panel. Frequency switching is performed on the rear side.
Advantages in operation
The time relay offers a wide adjustment range from 0.2 seconds to 60 hours, covering a wide range of application scenarios. The simple operation via the continuously variable rotary switch allows precise and quick adjustment. The mechanical time control is robust and low-maintenance. The time progress indicator facilitates monitoring of the timing sequence. The version without a switch position indicator is typical for the EH 7616 series, simplifying the front panel. The repeatability of ≤ ± 0.5 % ensures reliable performance in repeated processes.