| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts | 2 C/O contacts |
| Time function(s) | Fleeting on break, Fleeting on make, Fleeting on make and brake |
| Time range | 0,3 s - 0,6 s |
| Width | 22,5 mm |
| Type | MK 9988 |
| Variant |
| Contact equipping | 1 fleeting contact (changeover) |
| Nominal voltage | AC 110 V 50/60 Hz |
| Variant | Programmable: fleeting on make, fleeting on break, fleeting on make and brake |
The Dold wipe relay MK9988.51 is a programmable time relay for use in enclosures, designed for a rated voltage of AC 110 V at 50/60 Hz. It is used for time-controlled switching of electrical loads, particularly in systems requiring precise, repeatable delays during switching operations. The device features a
wipe contact (changeover), which, depending on programming, operates as an
on-delay wipe relay,
off-delay wipe relay, or
on- and off-delay wipe relay. The
wipe time is fixed at 0.3 to 0.6 seconds, with a
repeatability of less than ±5 %, ensuring high reliability during repeated switching operations.
Applications
The wipe relay is used in industrial control systems, for example, to delay the switching on or off of motors, heaters, or lighting systems. It is particularly suitable for applications requiring a short, defined delay to reduce mechanical stress or ensure the sequence of switching operations. Control is achieved via
two-wire initiators, which simplifies integration into existing sensor networks.
Functions and Equipment in Detail
The device is equipped with an
LED indicator for operational readiness, visually displaying the relay’s status. Programming is done via programming inputs X1, X2, and X3, where bridging the respective terminals selects the desired function (on-delay, off-delay, or on- and off-delay wipe). The contact configuration includes a
changeover, with the MK9988.51 variant standardly equipped with a wipe contact. The
width is 22.5 mm, enabling compact mounting in standard enclosures.
Technology Explained Simply
The
wipe function means the contact does not switch immediately, but transitions over a short period (0.3–0.6 s) from one position to another. This prevents mechanical stress and enables gentle switching. The
wipe time setting is factory-fixed, so no adjustments are required on the device. The
repeatability of less than ±5 % ensures the delay is nearly identical for each switching operation. The
rated voltage AC 110 V is suitable for applications in certain industrial countries or specific networks. The
voltage tolerance of -5 % to +10 % ensures stable operation even with slight fluctuations in supply voltage.
Compatibility and Accessories
The wipe relay is designed for use with
two-wire initiators, enabling compatibility with non-contact sensors such as inductive or capacitive sensors. The contact configuration is designed for a
changeover, with the MK9988.52 variant also available with two wipe contacts. Terminal marking follows EN 50005, and the conductor connection terminals are rated for 2 x 1.5 mm² solid or stranded wire with ferrules DIN 46228-1/-2/-3/-4. Wire stripping length is 8 mm.
Mounting and Installation
The device is mounted in enclosures, with a width of 22.5 mm allowing standard mounting on DIN rails. The connection terminals are flat and feature a self-lifting mechanism, ensuring a secure connection. Programming is done by bridging terminals X1, X2, and X3, with the exact combinations described in the datasheet. Mounting requires no special tools, and wiring follows the instructions in the circuit diagram.
Operational Advantages
The
programmable function allows flexible adaptation to different requirements without replacing the device. The
high repeatability ensures consistent switching operations, which is important in automated processes. The
LED indicator simplifies diagnosis and maintenance, as the operational status can be visually checked. The
short-circuit resistance with a maximum fuse rating of 6 A gG/gL protects the device and connected loads. The
mechanical life of 20 million switching operations and the
electrical life of 500,000 switching operations at 3 A/AC 230 V ensure long service life. The device is designed for
continuous operation and can be operated at temperatures from -20 °C to +60 °C. The
protection rating IP 40 for the housing and IP 20 for the terminals protects against contact and foreign objects, but not against splashing water or dust.
Technical Standards and Approvals
The device complies with the standard
IEC/EN 61812-1 for time relays. The
overvoltage category III and
insulation test voltage of 2.5 kV ensure safe insulation.
EMC requirements according to IEC/EN 61000-4-2 to -4-6 and
radio interference suppression class B (EN 55011) ensure low emission and high immunity. The
rated impulse voltage of 4 kV and
pollution degree 2 are suitable for industrial environments. The housing is made of
thermoplastic with V0 behaviour according to UL Subj. 94, indicating a high flame retardancy class.
Operating Conditions
The device is designed for operation at ambient temperatures from -20 °C to +60 °C, with storage up to +70 °C. Relative humidity must not exceed 93 % at 40 °C. The operating altitude is limited to below 2000 m.
Vibration resistance at an amplitude of 0.35 mm and frequencies from 10 to 55 Hz, as well as
climate resistance according to IEC/EN 60068-1 (20/060/04), ensure robust performance under industrial conditions.
Contact Technology and Switching Capacity
The contacts are made of
AgSnO₂, a material suitable for high switching life and low contact resistance. The switching capacity according to AC 15 is 3 A at AC 230 V for closing contacts and 1 A for opening contacts. The
rated operating voltage is AC 250 V, and the
thermal current Ith is specified as 5 A. The