| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts | 1 C/O contact |
| Time function(s) | On-delay |
| Width | 45 mm |
| Type | AA 7616 |
| Variant |
| Contact equipping | 1 changeover contact delayed, 1 changeover undelayed |
| Nominal voltage | AC 230 V |
| Time range | 0,15 - 1000 s |
| Variant | No-voltage safe |
The Dold time relay AA7616.32/100 is a delayed-actuation relay for use in enclosures, designed for time-controlled operation of devices and plant components. It enables the setting of delay times for activating loads, for example when starting electric motors, to minimize mechanical stress. The device operates according to standard EN 61812-1 and features a purely mechanical timing mechanism, which can be adjusted via stepless rotary switches on the front. The width is 45 mm, making it suitable for standard control panels.
Applications
This time relay is used in industrial controls, plant automation, and machine building, where precise timing sequences of switching operations are required. Typical applications include sequential switching of pumps, fans, or heating systems, as well as delaying protective functions in electrical installations. The voltage failure-safe feature ensures that the set delay time is not reset during short-term power interruptions, but retained, which is important for critical processes.
Functions and Equipment in Detail
The device features two output contacts: one delayed changeover contact (delayed-actuation) and one instantaneous changeover contact (immediate action). The delayed contacts switch only after the set time has elapsed, while the instantaneous contacts switch immediately upon actuation of the relay. The time ranges are adjustable in six switchable steps, with the current type covering a time range of 0.15 to 1000 seconds. Repeatability is ≤ ± 0.5 %, except in the 3 and 6 second range, where it is ≤ ± 1 %. A timing indicator with a red pointer on the scale shows the progress of the delay time. A switching position indicator is also present, except for the EH 7616 variant.
Technology Explained Simply
The timing mechanism is driven by a synchronous motor, powered by the control voltage at terminals A1–A2. The delay time is set via a rotary switch on the front, which adjusts the position of a mechanical drive regulator. In the voltage failure-safe version, the coupling is locked by a latch, so that the elapsed time is retained during power failure. Frequency switching between 50 Hz and 60 Hz is performed on the rear of the device by moving a catch with a screwdriver.
Compatibility and Accessories
The relay is designed for a nominal voltage of AC 230 V and can be mounted in enclosures with standard widths. It is part of the MINITIMER series from Dold and can be combined with other models in the series such as EC 7616, EF 7616, or EH 7616, depending on requirements for front panel area and required time range coverage. The EF 7616 variant, for example, features a front panel with IP 65 protection, making it suitable for environments protected against water jets.
Mounting and Installation
Mounting is done in standard control panels or enclosures. Terminals A1–A2 are intended for control and operating voltage, while B1–B2 can optionally be used for control voltage. The connection terminals are clearly labeled: 15–16 (delayed normally open), 27–28 (delayed normally closed), 31–32 (instantaneous normally open), 43–44 (instantaneous normally closed). The delay time is adjusted via the rotary switch on the front. For using the quick-start function (for short times), the AA 7616.32 version is required, where terminals A1–A2 are permanently connected to the nominal voltage.
Advantages in Operation
The relay offers a wide adjustment range from 0.15 to 1000 seconds, enabling flexible adaptation to different requirements. Simple operation via stepless rotary switches and high repeatability ensure reliable and reproducible switching operations. Voltage failure-safe operation increases reliability in critical applications, as the timing information is not lost during short-term power interruptions. The mechanical design without electronic components ensures high robustness and long service life.