| Technical data |
| Enclosure design | Switch cabinet |
| Time function(s) | Off-delay, with control signal |
| Width | 45 mm |
| Type | AA 7666 |
| Variant |
| Contact equipping | 1 NC contact delayed, 1 NO contact delayed |
| Nominal voltage | AC 230 V |
| Time range | 0,15 - 1000 s |
The Dold time relay AA7666.21 is a delayed-release industrial time relay, designed for use in enclosures. It is used for time-delayed control of electrical devices and system components, particularly to account for coast-down behavior, such as in motors. The function is based on a purely mechanical timing mechanism, which can be easily and precisely adjusted via a continuously variable rotary switch on the front panel. The time delay occurs after switching off the control signal, with the contacts only switching after the set time has elapsed. This enables controlled switching off of loads to minimize mechanical stress or energy loss.
Applications
This device is suitable for applications in industrial automation and control technology where a targeted delay during switching off is required. Examples include controlling fans, pumps, lighting systems, or other equipment that requires a short operating time after switching off. The delayed-release function is often used to gently switch off mechanical components or to ensure that one device is fully switched off before another system is activated.
Functions and Equipment in Detail
The time relay features contact configuration with one delayed opener and one delayed closer. The delay time can be set in the range of 0.15 to 1000 seconds, with six switchable time ranges available. Adjustment is performed via a continuously variable rotary switch on the front panel, positioned on an absolute scale. The repeatability is ≤ ± 0.5 % of the scale end value, with a deviation of ≤ ± 1 % allowed in the 3 and 6 second ranges. A time delay indicator visually signals the progress of the set delay time. The contact position indicator shows the current state of the contacts, which is available in the AA 7666 variant.
Technology Explained Simply
The technology is based on a mechanical timing mechanism operating via spring or weight control. When the control signal is switched off, the timing begins, and the contacts only switch after the set time has elapsed. The zero-voltage safety ensures that the relay immediately returns to its rest state in case of power failure. The response time of the contacts is less than 35 ms, and the release time is under 60 ms. The maximum thermal current rating is 4 A. The device is designed for a rated voltage of AC 230 V, with a voltage range of 0.8 to 1.1 times the rated voltage. The rated frequency is 50/60 Hz, with frequency influence being inversely proportional.
Compatibility and Accessories
The time relay is designed for use in enclosures and conforms to the enclosure form for panel mounting. The width is 45 mm, making it suitable for standard control panels. It is compatible with control systems providing AC 230 V voltage. The contact configuration allows use in circuits requiring delayed switching off. The EN 61812-1 standard is fulfilled for the timing function, ensuring reliability and safety in industrial applications.
Mounting and Installation
Mounting is performed in an enclosure using the provided mounting elements. The connection terminals are designed for wiring, with maximum switching capacity according to AC 15 at 3 A and AC 230 V. The permissible switching frequency is 3000 switching operations per hour. The short-circuit resistance requires a maximum fuse rating of 10 A gG/gL. The mechanical life exceeds 30 million switching operations or 15,000 operating hours.
Advantages in Operation
Operation of the time relay is characterized by its simple adjustment and high repeatability. The continuous adjustment allows precise adaptation to specific requirements. The zero-voltage safety increases operational safety, as the device reacts immediately in case of power failure. The mechanical life and high electrical life ensure long service life with minimal maintenance. Front-side adjustment and visual indicators simplify commissioning and maintenance.