| Technical data |
| Enclosure design | Front panel mounting |
| Output contacts | 1 C/O contact |
| Time function(s) | On-delay |
| Width | 96 mm |
| Type | EH 7616 |
| Variant |
| Contact equipping | 1 NC contact delayed, 1 NC contact undelayed, 1 NO contact delayed, 1 NO contact undelayed |
| Nominal voltage | AC 230 V |
| Time range | 0,2 s - 60 h |
The Dold time relay EH7616.24 is a delayed-on time relay of the MINITIMER series, designed for use in industrial control and switching systems. It is used for time-delayed activation of devices and components, for example during motor start-up, to account for the individual start-up behavior of the system. The device features a purely mechanical time delay, which can be easily and precisely adjusted via stepless rotary switches on the front panel. The rated voltage is AC 230 V, and the time range extends from 0.2 seconds to 60 hours, with six switchable time ranges available. The repeatability is ≤ ± 0.5 %, with a deviation of ≤ ± 1 % allowed in the 3 and 6 second ranges. The time delay indication is provided by a red pointer on the device scale, visually displaying the progress of the set delay time.
Applications
This time relay is designed for applications in industrial automation and control technology where a controlled time-delayed switching function is required. Typical applications include sequential actuation of system components, avoiding current surges during motor start-up, or maintaining safety distances in production processes. The front panel mounting form enables simple installation in enclosures and control cabinets. The width of 96 mm corresponds to the standard format for front panel mounted devices and ensures compatible placement in existing switching systems.
Functions and Equipment in Detail
The device features contact configuration with one delayed normally open contact, one instantaneous normally open contact, one delayed normally closed contact, and one instantaneous normally closed contact. This configuration allows parallel control of multiple loads with different time delays. The output contacts are configured as 1 changeover, where the delayed contacts switch only after the set time has elapsed, while the instantaneous contacts react immediately. The switching position indicator is not available for this device type, as explicitly stated in the product description. The time function is delayed-on, meaning the delay time begins only after the control voltage is applied.
Technology Explained Simply
The time delay is based on a purely mechanical principle driven by a synchronous motor. The delay time is selected via a stepless rotary switch on the front panel, with the time ranges chosen by switching between the six predefined ranges. The frequency switching between 50 Hz and 60 Hz is performed on the rear of the device by moving a latch with a screwdriver. The time delay indication is provided by a red pointer moving along a scale, visually displaying the progress of the delay time. The contacts are designed to retain their position in case of voltage failure if a voltage-fail-safe version is selected — however, this is not standard for this model.
Compatibility and Accessories
The device is designed for use in enclosures and control systems that support front panel mounting. It is compatible with other devices from the MINITIMER series, particularly models AA 7616, EC 7616, and EF 7616, which also offer delayed-on time functions. Terminal markings are standardized: A1-A2 serve as control and operating voltage, B1-B2 as control voltage for the voltage-fail-safe variant (not applicable for this model), and contacts 15-16, 27-28, 31-32, 43-44 serve as delayed and instantaneous normally open and normally closed contacts. The devices are specified according to EN 61812-1, meeting requirements for time relays in industrial applications.
Mounting and Installation
Mounting is performed via front panel installation in an enclosure or control cabinet. The width of 96 mm corresponds to the standard format, so installation conditions are typically met without additional modifications. The connection terminals are clearly labeled, with control voltage connected to A1-A2. Frequency switching is performed on the rear of the device by moving the latch with a screwdriver. The delay time setting is adjusted via the rotary switch on the front panel, with time ranges selected by switching.
Operational Advantages
The device offers a wide adjustment range from 0.2 seconds to 60 hours, enabling flexible adaptation to different applications. Simple operation via stepless rotary switches and visual time delay indication facilitate commissioning and maintenance. The purely mechanical time control ensures high reliability and repeatability. The front panel mounting form and standard width of 96 mm ensure easy integration into existing switching systems. The time function is delayed-on, which represents the desired switching logic for many industrial applications.