| Technical data |
| 1- / 3-phase | 1 |
| Auxiliary voltage | Without |
| Enclosure design | Switch cabinet |
| Output contacts | 1 C/O contact |
| Width | 45 mm |
| Type | AI 838 |
| Variant |
| Contact equipping | 1 changeover contact |
| Measuring range | AC 50/60 Hz 2,5 - 5 A |
The Dold overcurrent relay AI 838 AC50/60HZ 2,5-5A is a single-phase measuring relay for monitoring alternating current circuits in the range of 2.5 to 5 A at a frequency of 50/60 Hz. It serves for electrical protection and signal indication when exceeding a set operating threshold. The device is designed for use in enclosures and has a width of 45 mm, making it suitable for standard control panels. The relay's scale is adjusted to the operating threshold, so the relay activates as soon as the measured current exceeds this value. It returns to its resting position when the current falls below the reset value — calculated as the operating threshold multiplied by the reset ratio. This hysteresis ensures stable switching behavior without unwanted oscillations.
Applications
The AI 838 is used in industrial plants where continuous monitoring of current circuits is required, for example in machine controls, drive technology, or for monitoring motors and transformer connections. It is particularly suitable for applications where safe and reliable overload protection is necessary without requiring an external auxiliary voltage. The direct measurement in the range of 2.5 to 5 A makes it suitable for small to medium power applications.
Functions and Equipment in Detail
The relay features a single changeover contact as output contact, which changes its state when the relay operates. The operating threshold setting is continuous and is adjusted internally on the device. The reset ratios for alternating current are approximately 0.8 at the beginning of the scale and 0.9 in the middle or at the end of the scale. For direct current with a ripple content of less than 5 %, the reset ratio is approximately 0.6 at the beginning of the scale and 0.7 in the middle or at the end. The repeatability accuracy is ≤ ±2 % for alternating current and ≤15 % for direct current. The switching delay is approximately 100 ms, with longer delays achievable by connecting a time or delay relay in series.
Technology Explained Simply
The device operates without auxiliary voltage, meaning it is powered directly from the monitored current circuit. Measurement is performed via the input terminals i and k, which are connected into the current circuit. The internal resistance values vary depending on the measurement range; for the 2.5–5 A range, the internal resistance is 0.089 Ω (AI 837) or 0.166 Ω (AI 838). The overload capacity is defined for continuous operation up to 12 A at a factor of 1.0 times the scale end value. For short durations (1 second), the relay can be loaded up to 2.0 times the scale end value. The thermal current rating (Ith) is 6 A.
Compatibility and Accessories
For measurement ranges above 16 A, the relay can be extended by inserting a current transformer. For example, a current transformer with a secondary rated current of 5 A and a rated power of 18 VA can be used, such as those offered by Ritz Instrument Transformers GmbH (e.g., type KSW 73). For direct current applications, a parallel connection of a shunt in the range of 8–16 A is possible. The specifications for extending the measurement range refer to a supply line with a resistance of approximately 0.5 mΩ (corresponding to 0.30 m length with 10 mm² cross-section made of E-Cu) and an ambient temperature of 20 °C.
Mounting and Installation
The relay is mounted in enclosures and requires direct integration into the circuit to be monitored. Terminals i and k serve as the current measurement input, while contacts 11, 12, and 14 form the changeover contact. Mounting is done in standard control panels with a width of 45 mm. The electrical service life is up to 5 million switching operations at a switching frequency of 3000 operations per hour and 30 % of switching capacity. At higher loads, the service life decreases accordingly.
Advantages in Operation
The AI 838 is characterized by high reliability and easy handling. The continuous adjustment of the operating threshold allows precise adaptation to the specific application. The ability to operate without auxiliary voltage reduces installation complexity and lowers supply requirements. The electrical service life and high switching durability make it suitable for industrial operating conditions. Compliance with the standard IEC/EN 60255-1 ensures standardized quality and safety.
Rated Consumption and Switching Capacity
The rated consumption for alternating current is less than 18 VA. The rated switching capacity for alternating voltage (AC) is 24 V, 110 V, 230 V, and 380 V with a cos φ of 1 to 0.7 at 4 A and cos φ 0.4 at 3 A. For direct voltage (DC), the switching capacity is 1 A, 0.4 A, 0.3 A, and 0.15 A for resistive loads at 24 V, 60 V, 110 V, and 220 V, and 0.5 A, 0.2 A, 0.15 A, and 0.08 A for inductive loads. The maximum short-circuit withstand capacity is 10 A gG/gL according to IEC/EN 60947-5-1.
Approvals and Markings
The device meets the requirements of the standard IEC/EN 60255-1 and is suitable for use in industrial plants. Technical data and approvals are documented in the manufacturer's data sheet.