| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts | 1 C/O contact |
| Time function(s) | On-delay |
| Width | 45 mm |
| Type | AA 7616 |
| Variant |
| Contact equipping | 1 changeover contact delayed, 1 changeover undelayed |
| Nominal voltage | AC 230 V |
| Time range | 0,2 s - 60 h |
The Dold time relay AA7616.32 is a delayed-action relay for use in enclosures, designed for a rated voltage of AC 230 V and a frequency of 50/60 Hz. It is used for time-controlled operation of devices and system components, for example, for controlled motor start-up or for coordinating process steps in industrial control systems. The device features a wide adjustment range from 0.2 seconds to 60 hours, which can be continuously adjusted front-side via six switchable time ranges. The time function is purely mechanical and based on a synchronous motor, which is connected to the operating voltage via control terminals A1-A2. The delay time begins as soon as the control voltage is applied to terminals B1-B2.
Applications
The time relay AA7616.32 is designed for applications in industrial environments where precise timing of switching operations is required. Typical applications include the control of pumps, fans, heating systems, or motor protection through delayed switching. The ability to adjust the delay time over a wide range from milliseconds to hours makes the device flexible for various process requirements. The width of 45 mm allows for compact mounting in standard enclosures.
Functions and Features in Detail
The device features two output contacts: one delayed changeover contact (15-16, 27-28) and one instantaneous changeover contact (31-32, 43-44). The delayed contacts switch only after the set delay time has elapsed, while the instantaneous contacts switch immediately upon activation. The repeatability is ≤ ± 0.5 %, with a permissible deviation of ≤ ± 1 % in the 3 and 6 second ranges. A time progress indicator with a red pointer on the device scale shows the progress of the delay time. A switching position indicator is also integrated, although not available in the EH 7616 variant.
Technology Explained Simply
The time control is purely mechanical, operated by a synchronous motor that runs continuously as long as the operating voltage is applied to terminals A1-A2. The delay time is adjusted via a rotary switch, which controls the motor speed through a gear and coupling. If the control voltage at B1-B2 is interrupted, the time sequence is reset. The frequency switching between 50 Hz and 60 Hz is performed on the rear of the device by moving a latch with a screwdriver. The AA 7616.32 version supports a quick start, where terminals A1-A2 remain permanently energized to improve repeatability for short delay times.
Compatibility and Accessories
The time relay AA7616.32 is part of Dold’s MINITIMER series and can be combined with other models in the series such as EC 7616, EF 7616, and EH 7616, depending on requirements for front panel area and width. The devices comply with standard EN 61812-1 and are suitable for use in industrial control systems. A voltage-loss-safe version is optionally available, in which the elapsed time is retained in case of power failure.
Mounting and Installation
The device is mounted in enclosures and requires a width of 45 mm. The connection terminals are clearly labeled: A1-A2 for operating voltage, B1-B2 for control voltage, and contact terminals 15-16, 27-28, 31-32, 43-44 for output contacts. The delay time is adjusted via the front-side rotary switch, which switches between the six time ranges. Frequency switching is performed on the rear of the device.
Operational Advantages
The combination of a wide adjustment range, high repeatability, and easy operation makes the AA7616.32 a reliable component in industrial control systems. The mechanical time control is robust and requires little maintenance. The clear display of time progress and switching position facilitates commissioning and maintenance. The ability to adjust the delay time over a wide range offers flexibility when adapting to different processes. The voltage-loss safety feature (optional) ensures that the set time is not lost during short-term power outages.