Dold 0000697, EAN: 4030641006976

Dold 0000697 AA7616.32AC50/60HZ230V0,15S-30H time relay delayed-on

Industrial Material > Industrial relays and contactors > Industrial Timers

Dold 0000697 AA7616.32AC50/60HZ230V0,15S-30H time relay delayed-on

Lieske Part No. 328012
Mfg Part No 0000697
EAN-Code 4030641006976
Manufacturer Dold
Here only 263,95 EUR
314,10 EUR incl. VAT

Further information for Dold 0000697 AA7616.32AC50/60HZ230V0,15S-30H time relay delayed-on

Technical data
Enclosure designSwitch cabinet
Output contacts1 C/O contact
Time function(s)On-delay
Width45 mm
TypeAA 7616
Variant
Contact equipping1 changeover contact delayed, 1 changeover undelayed
Nominal voltageAC 230 V
Time range0,15 s - 30 h
The Dold time relay AA7616.32AC50/60HZ230V0,15S-30H is a delayed-on time relay from the MINITIMER series, designed for use in industrial control systems and enclosures. It is used for time-delayed activation of electrical loads, for example during motor start-up, to account for the individual starting behaviour of system components. The device operates at a rated voltage of AC 230 V and features an adjustable time range from 0.15 seconds to 30 hours. The delay time is set via a continuously variable rotary switch on the front, allowing precise and flexible adaptation to different applications.

Applications
This time relay is designed for use in industrial plants, machine control systems, and automation systems. It is particularly suitable for applications requiring controlled, time-delayed switching functions, such as sequential switching of components in a production line or motor protection against too rapid start-up. Its robust enclosure design for use in enclosures enables easy installation in existing electrical systems.

Functions and Features in Detail
The device features two output contacts: one delayed changeover contact and one non-delayed changeover contact, enabling both time-delayed and immediate switching operations. The delayed contacts switch only after the set delay time has elapsed, while the non-delayed contacts respond immediately upon activation. The repeatability is ≤ ± 0.5 %, with a permissible deviation of ≤ ± 1 % in the 3 and 6 second ranges. A time progress indicator with a red pointer on the device scale allows visual monitoring of the time progression. The switching position indicator is also integrated, although not available on the EH 7616 variant.

Technology Explained Simply
The time relay operates on a purely mechanical time delay driven by a synchronous motor. The delay time is determined by the motor speed and the position of the adjustment knob. Frequency switching between 50 Hz and 60 Hz is performed on the rear of the device by moving a latch with a screwdriver. The width is 45 mm, enabling compact installation in standard enclosures. The time function is delayed-on, meaning the contacts switch only after the set time has elapsed once the control voltage is applied.

Compatibility and Accessories
The device is part of the MINITIMER series and can be combined with other models such as EC 7616, EF 7616, and EH 7616, depending on requirements for front panel size and housing dimensions. The EF 7616 variant features a spray-water protected front (IP 65), suitable for use in damp environments. The AA 7616.32 is specifically designed for fast start-up, where terminals A1-A2 remain permanently connected to the rated voltage, while the time delay is initiated via terminals B1-B2 to improve repeatability.

Mounting and Installation
The device is mounted in enclosures and requires secure fastening to an appropriate mounting rail. The connection terminals are clearly marked: A1-A2 are for control and operating voltage, B1-B2 for control voltage in versions with a separate start contact. Contacts 15-16 (normally open delayed), 27-28 (normally closed delayed), 31-32 (normally open non-delayed), and 43-44 (normally closed non-delayed) allow flexible wiring. Frequency switching is performed manually on the rear.

Operational Advantages
The continuously adjustable setting over a wide time range from 0.15 seconds to 30 hours offers flexibility for diverse applications. High repeatability and mechanical reliability ensure stable operating results. The integrated time progress indicator and switching position indicator simplify commissioning and maintenance. The device complies with the standard EN 61812-1 for delayed-on time relays, ensuring adherence to safety and quality standards.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/328012
qrcode für Dold 0000697 AA7616.32AC50/60HZ230V0,15S-30H time relay delayed-on