| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts | 1 C/O contact |
| Time function(s) | On-delay |
| Width | 45 mm |
| Type | AA 7616 |
| Variant |
| Contact equipping | 1 changeover contact delayed, 1 changeover undelayed |
| Nominal voltage | AC 230 V |
| Time range | 0,15 - 1000 s |
The Dold time relay AA7616.32 is a delayed-actuation relay for use in industrial control systems and switchgear. It is designed for time-delayed activation of switching operations, for example during motor start-up or for coordinating process steps in automation systems. The device is rated for a nominal voltage of AC 230 V and features a time range of 0.15 to 1000 seconds. The width is 45 mm, making it suitable for installation in standard enclosures. The time function operates purely mechanically, with the delay time adjusted via a continuous rotary switch on the front panel. The repeatability is ≤ ± 0.5 %, with a deviation of ≤ ± 1 % allowed in the 3 and 6 second ranges. The time progression is indicated by a red pointer on the device scale, visually displaying the progress of the set delay time.
Applications
The time relay AA7616.32 is used in industrial plants where controlled temporal sequencing of switching operations is required. Typical applications include step-by-step motor start-up, signal delay in control circuits, or synchronization of machine components in manufacturing processes. The delayed-actuation function ensures that the output contacts only switch after the set time has elapsed, enabling precise control.
Functions and Features in Detail
The device features two output contacts: one delayed changeover contact and one instantaneous changeover contact. The delayed contact switches only after the set time has elapsed, while the instantaneous contact reacts immediately upon application of the control voltage. This contact configuration allows parallel control of two different loads with different timing characteristics. The switching position indicator is integrated, although not available in the EH 7616 variant. The time progression is visible via a red pointer on the scale, indicating the progress of the delay time.
Technology Explained Simply
The time control operates purely mechanically via a synchronous motor, driven by the control voltage connected to terminals A1-A2. The delay time is adjusted using a rotary switch, which reduces the motor speed via a gear train and gear mechanism. The time progression is shown by a red-marked pointer. If the control voltage at A1-A2 is interrupted, the time sequence is reset; an interruption at B1-B2 extends the delay time by the duration of the interruption. Frequency switching between 50 Hz and 60 Hz is performed on the rear of the device by moving a latch with a screwdriver.
Compatibility and Accessories
The time relay AA7616.32 is part of Dold’s MINITIMER series and can be combined with other models in the series such as EC 7616, EF 7616, and EH 7616, depending on requirements for width and front panel area. The devices comply with EN 61812-1 standards and are suitable for use in enclosures. A voltage-loss-safe version is optionally available, retaining the elapsed time during power failure. Terminal markings follow the standard: A1-A2 for control voltage, B1-B2 for additional control voltage, and contacts 15-16, 27-28, 31-32, 43-44 for output contacts.
Mounting and Installation
The device is installed in enclosures with a width of 45 mm. Mounting is done via screw fastening to the enclosure wall. The connection terminals are clearly labeled, with the control voltage connected to A1-A2. When using the voltage-loss-safe variant, additional control voltage must be connected to B1-B2. Frequency switching is performed on the rear of the device. The delay time is adjusted using the rotary switch on the front panel.
Operational Advantages
The purely mechanical time control offers high reliability and repeatability. The wide adjustment range of 0.15 to 1000 seconds allows flexible adaptation to various applications. The visual time progression indicator facilitates monitoring of the switching process. Simple operation via continuous rotary switches reduces setup time and minimizes errors. Compatibility with other models in the MINITIMER series enables modular expansion of control systems.