| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts | 1 C/O contact |
| Time function(s) | On-delay |
| Width | 45 mm |
| Type | AA 7616 |
| Variant |
| Contact equipping | 1 NC contact delayed, 1 NC contact undelayed, 1 NO contact delayed, 1 NO contact undelayed |
| Nominal voltage | AC 240 V |
| Time range | 0,2 s - 60 h |
The Dold time relay AA7616.24 is a delayed-on time relay for use in enclosures, designed for a rated voltage of AC 240 V and a frequency of 50/60 Hz. It is used for time-controlled operation of devices and system components, for example, for controlled motor start-up or for coordinating switching operations in industrial processes. The delay time can be continuously adjusted within a range of 0.2 seconds to 60 hours, with a repeatability of ≤ ± 0.5 % (≤ ± 1 % in the range of 3 and 6 seconds). The time function operates purely mechanically, ensuring high reliability and low dependence on electronic components.
Applications
This device is designed for industrial control tasks where precise temporal dependency between the switching operation and the execution of a function is required. Typical applications include controlling pumps, fans, lighting systems, or other electrical loads where immediate switching is not desired. The ability to adjust the delay time over a wide range makes the relay flexible for use in various system configurations.
Functions and Equipment in Detail
The time relay features contact configuration with one delayed normally open contact, one immediate normally open contact, one delayed normally closed contact, and one immediate normally closed contact, which together correspond to one output contact in the form of a changeover. The delay is adjusted via a continuous rotary switch on the front panel, which enables six selectable time ranges. A time progress indicator with a red pointer on the device scale visually displays the progress of the set delay time. A switching position indicator is also present, except for the EH 7616 variant. The contacts are designed to retain their position in case of power failure if a voltage-fail-safe version is selected.
Technology Explained Simply
The time control is based on a purely mechanical principle, where a synchronous motor realizes the time delay via a mechanical drive. Adjustment is made via a rotary switch that influences the motor speed and thus varies the delay time. The time progress indicator visually shows the progress of the delay, enabling monitoring of operation. The contacts switch after the set time has elapsed, with delayed contacts switching only after the delay period, while immediate contacts react instantly.
Compatibility and Accessories
The relay is designed for use in enclosures and has a width of 45 mm. It complies with standard EN 61812-1 for delayed-on time relays. Frequency switching between 50 Hz and 60 Hz is performed at the rear of the device by shifting a latch using a screwdriver. The AA 7616.32 version enables a quick start, where the time delay control is initiated via separate terminals B1-B2, while terminals A1-A2 remain permanently connected to the operating voltage.
Mounting and Installation
The device is installed in an enclosure, with a width of 45 mm allowing mounting in standard control panels. The connection terminals are clearly labeled: A1-A2 for control and operating voltage, B1-B2 optionally for control voltage in voltage-fail-safe versions, and contact terminals 15-16 (delayed normally open), 27-28 (delayed normally closed), 31-32 (immediate normally open), 43-44 (immediate normally closed). The delay time is adjusted via the rotary switch on the front panel.
Advantages in Operation
The combination of a wide adjustment range, simple operation, and high repeatability makes the relay a reliable solution for time-controlled applications. The mechanical time control is robust and independent of electronic components, increasing service life and operational safety. The visual display of the time progress facilitates monitoring and maintenance of the device during operation. The ability to adjust the delay time across six ranges offers flexibility in adapting to different requirements.