Dold 0000680, EAN: 4030641006808

Dold 0000680 time relay delayed response 230V

Industrial Material > Industrial relays and contactors > Industrial Timers

Dold 0000680 time relay delayed response 230V

Lieske Part No. 841315
Mfg Part No 0000680
EAN-Code 4030641006808
Manufacturer Dold
Here only 283,98 EUR
337,94 EUR incl. VAT

Further information for Dold 0000680 time relay delayed response 230V

Technical data
Enclosure designSwitch cabinet
Output contacts1 C/O contact
Time function(s)On-delay
Width45 mm
TypeAA 7616
Variant
Contact equipping1 NC contact delayed, 1 NC contact undelayed, 1 NO contact delayed, 1 NO contact undelayed
Nominal voltageAC 240 V
Time range0,2 s - 60 h
The Dold time relay AA7616.24 is an on-delay relay for use in industrial control systems and switchgear. It is used for time-delayed activation of switching operations, for example when starting motors or coordinating process steps in production plants. The device operates according to the standard EN 61812-1 and features a purely mechanical time delay, which is adjusted via stepless rotary switches on the front. The delay time can be set in the range from 0.2 seconds to 60 hours, with a repeatability of ≤ ± 0.5 % (≤ ± 1 % in the range of 3 s and 6 s). The width is 45 mm, making it suitable for installation in standard enclosures.

Applications
The time relay AA7616.24 is used in industrial plants where a controlled temporal sequence of switching operations is required. Typical applications include starting electric motors, controlling pumps, coordinating conveyor belts, or synchronizing multiple components in a production line. The ability to adjust the delay time continuously over a wide range enables flexible adaptation to different process requirements.

Functions and Equipment in Detail
The device features contact configuration with one delayed normally open contact, one instantaneous normally open contact, one delayed normally closed contact, and one instantaneous normally closed contact. This corresponds to an output contact type of 1 changeover. The delayed contacts switch only after the set time has elapsed, while the instantaneous contacts switch immediately upon actuation. A time delay indicator with a red pointer on the device scale shows the progress of the delay time. A switching position indicator is also present, although not on the EH 7616 variant. Adjustment is made via six switchable time ranges, accessible from the front.

Technology Explained Simply
The time delay is based on a purely mechanical principle, where a synchronous motor realizes the time delay via a mechanical coupling and gear train. The operating voltage is AC 240 V, with the frequency switchable between 50/60 Hz, which is adjusted on the rear of the device using a screwdriver. The delay time is adjusted via a stepless rotary switch, covering six different ranges. If the operating voltage at terminals A1-A2 is interrupted, the time delay is reset. However, if only the control voltage at B1-B2 is interrupted, the delay time is extended by the duration of the interruption.

Compatibility and Accessories
The device is designed for installation in enclosures and corresponds to the enclosure form type enclosure. It is part of the MINITIMER series from Dold and can be combined with other models in the series such as EC 7616, EF 7616, or EH 7616, depending on requirements for front panel area and width. The AA 7616 variant is designed with a width of 45 mm, enabling compact mounting. The voltage-proof version is available as an option, in which the elapsed time is retained in case of power failure.

Mounting and Installation
Mounting is performed in standard enclosures using the provided mounting elements. The connection terminals are clearly labeled: A1-A2 for operating voltage, B1-B2 for control voltage (in versions with B1-B2), and contact terminals 15-16 (delayed normally open), 27-28 (delayed normally closed), 31-32 (instantaneous normally open), and 43-44 (instantaneous normally closed). The delay time is adjusted via the rotary switches on the front. The 50/60 Hz frequency switching is performed on the rear of the device.

Advantages in Operation
The stepless adjustment of the delay time over a wide range from 0.2 s to 60 h enables precise adaptation to different requirements. The high repeatability of ≤ ± 0.5 % ensures reliable and reproducible switching operations. The mechanical design is robust and low-maintenance. The time delay indicator and switching position indicator facilitate monitoring of the operating status. The ability to switch the frequency between 50/60 Hz increases flexibility during installation in different power grid environments. The voltage-proof version (optional) ensures that the set time is not lost in case of power failure, which is advantageous in critical applications.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/841315
qrcode für Dold 0000680 time relay delayed response 230V