Further information for DEHN 999906 DCOR L 2P SN1864 cable
Technical data
SPD according to EN 61643-11 / IEC 61643-11
Type 2 / Class II
Energy-coordinated protective effect to end device (≤ 10 m)
Type 2 + Type 3
Nominal voltage AC (UN)
230 V (50 / 60 Hz)
Maximum continuous operating voltage AC [L-N] (UC)
275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In)
5 kA
Maximum discharge current (8/20 µs) (Imax)
10 kA
Protection level [L-N] (UP)
≤ 1,5 kV
Protection level [L-N] at 3 kA (UP)
≤ 1 kV
Protection level [L-N] at 1.5 kA (UP)
≤ 0,85 kV
Response time [L-N] (tA)
≤ 25 ns
Maximum load current AC (IL)
10 A
Max. mains-side overcurrent protection
B 16 A
Short-circuit withstand capability with network-side overcurrent protection (ISCCR)
1 kAeff
Short-circuit withstand capability with network-side overcurrent protection with 16 A gG (ISCCR)
6 kAeff
TOV voltage [L-N] (UT) – characteristic
335 V / 5 sec. – withstand, 440 V / 120 min. – safe failure
Fault indication
Red
Number of ports
1
Operating temperature range (TU)
-40 °C ... +80 °C
Connection stranded wires
1.5 mm2, length 60 mm
Housing material
Thermoplastic, colour red, UL 94 V-2
Mounting position
indoor, luminaire head / cable transition box for mast mounting
Degree of protection in installed state
IP 20
Additional tests
---------------------------------
Total discharge surge current (Isum)
20 kA
Interruption of load circuit in fault condition
Two-pole surge arrester DEHNcord L, type 2 according to EN 61643-11, in a compact design for use in cable junction boxes of LED mast lights with shutdown of the load circuit in the event of a fault and protection of the control phase. For use in the lightning protection zone concept at the interfaces 0B - 1 and higher.