| General |
| SPD as per IEC 61643-41 / EN IEC 61643-41 | Type 2 |
| Energy coordination with terminal equipment (≤ 10 m) | type 2 + type 3 |
| Nominal voltage (d.c.) (UN) | 750 V |
| Max. continuous operating voltage DC (UC) | 900 V |
| Nominal discharge current (8/20 µs) (In) | 12.5 kA |
| Voltage protection level (UP) | ≤ 3.0 kV |
| Response time (tA) | ≤ 25 ns |
| Short-circuit withstand capability without backup fuse (d.c.) (ISCCR) | 100 A |
| Short-circuit withstand capability for max. mains-side overcurrent protection (d.c.) (ISCCR) | 5 kA |
| Max. mains-side overcurrent protection | 63 A gG |
| TOV (DC), 1.5x (UT) – characteristics | 1,238 V / 5 sec. – withstand |
| TOV (DC), 2x (UT) – characteristics | 1,650 V / 120 min. – safe failure |
| Continuous current (DC) (IC) | ≤ 100 µA |
| Protective conductor current (DC) (IPE) | ≤ 100 µA |
| Protective conductor current (AC) (IPE) | < 1 mA |
| Condition at the end of life time of the SPD A | Open Circuit Mode (OCM) |
| Overvoltage category (OVC) main circuit | lll |
| Insulation between main and remote circuit | Double insulation |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (min.) | 1.5 mm2 solid / fine-stranded / 6 mm2 stranded |
| Cross-sectional area (max.) | 16 mm2 solid / 35 mm2 stranded / 25 mm2 fine-stranded |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IP20 |
| Capacity | 1.5 Standard DIN module, DIN 43880 |
| Type of remote signalling contact | changeover contact |
| Switching capacity (a.c.) | 250 V / 0.5 A |
| Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
| Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
| Extended technical data |
| Max. prospective short-circuit current (DC) (Ik) | 25 kA |
Single-pole surge arrester DEHNguard SE DC, type 2 according to EN 61643-11, consisting of a base part and a plugged-in protection module. High device safety thanks to the powerful DC switching device DCD, which is specially designed for use in DC circuits. For protecting DC consumer systems against overvoltages. For use in the lightning protection zone concept at the interfaces 0B - 1 and higher.