General SPD classification as per EN 61643-11 / ... IEC 61643-11 type 2 / class II Energy coordination with terminal equipment (≤ 10 m) type 2 + type 3 Nominal voltage (d.c.) (UN) 220 V Max. continuous operating voltage DC (UC) 242 V Nominal discharge current (8/20 µs) (In) 12.5 kA Voltage protection level (UP) ≤ 1.25 kV Response time (tA) ≤ 25 ns Short-circuit withstand capability without backup fuse (d.c.) (ISCCR) 300 A Short-circuit withstand capability for max. mains-side overcurrent protection (d.c.) (ISCCR) 25 kA Max. mains-side overcurrent protection 35 A gG Temporary overvoltage (TOV) DC (UT) – characteristic 320 V / 5 sec. – withstand Temporary overvoltage (TOV) DC, 2x UC (UT) – characteristic 484 V / 120 min. – safe failure Operating temperature range (TU) -40 °C ... +80 °C Operating state / fault indication green / red Number of ports 1 Cross-sectional area (min.) 1.5 mm2 solid / flexible Cross-sectional area (max.) 35 mm2 stranded / 25 mm2 flexible For mounting on 35 mm DINs rails acc. to EN 60715 Enclosure material thermoplastic, red, UL 94 V-0 Place of installation indoor installation Degree of protection IP20 Capacity 1.5 Standard DIN module, DIN 43880 Extended technical data Max. continuous voltage (a.c.) (UC) 255 V DC and AC operation possible yes
Single-pole surge arrester DEHNguard SE DC, type 2 according to EN 61643-11, consisting of a base part and a plugged-in protection module. High device safety thanks to the powerful DC switching device DCD, which is specially designed for use in DC circuits. For protecting DC consumer systems against overvoltages. For use in the lightning protection zone concept at the interfaces 0B - 1 and higher.