| General |
| Degree of protection | Type 2 |
| Norm | EN 61643-11 |
| Monitoring technology | Thermo-Dynamik-Control |
| Network configuration | TN-S |
| Number of poles | 4 |
| Use in lightning protection zone concept | interfaces 0B - 1 and higher |
| Arrester use at 16.7 Hz – traction power supply systems |
| Test voltage AC (UC) | 275 V |
| Nominal AC voltage (UN) | 230 / 400 V |
| Nominal frequency AC (fN) | 16.7 Hz |
| Standards |
| Certification | UL |
| UL Standard | UL 1449 5th edition |
| UL File Number | E319777 |
| Technical data |
| Energy coordination with terminal equipment (≤ 10 m) | type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 230 / 400 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 275 V (50 / 60 Hz) |
| Nominal discharge current (8/20 µs) (In) | 20 kA |
| Max. discharge current (8/20 µs) (Imax) | 40 kA |
| Voltage protection level [L-PE]/[N-PE] (UP) | ≤ 1.5 / ≤ 1.5 kV |
| Voltage protection level [L-PE]/[N-PE] at 5 kA (UP) | ≤ 1 / ≤ 1 kV |
| Response time (tA) | ≤ 25 ns |
| Max. mains-side overcurrent protection | 125 A gG |
| Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR) | 50 kArms |
| Temporary overvoltage (UT) – characteristic | 335 V / 5 sec. – Festigkeit, 440 V / 120 min. – sicherer Ausfall |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (min.) | 1.5 mm2 solid / flexible |
| Cross-sectional area (max.) | 35 mm2 stranded / 25 mm2 flexible |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IP 20 (integrated) |
| Capacity | 4 Standard DIN module, DIN 43880 |
| Approvals | DEKRA, VDE, UL |
| Type of remote signalling contact | changeover contact |
| Switching capacity (a.c.) | 250 V / 0.5 A |
| Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
| Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
| Test values according to UL 1449 |
| Rated Voltage (AC, 50/60 Hz) | 230 V |
| MCOV (AC, 50/60 Hz) [L-N]/[L-G]/[N-G] | 275 V |
| Voltage protection rating (VPR) | ≤ 700 V |
| Nominal discharge current (8/20µs) ( In) | 20 kA |
| Maximum ambient temperature | 85 °C |
| UL 1449 edition | 5th edition |
| Type (SPD classification) | Type 4 component assembly |
The DEHNguard M TNS 275 FM is a multipole surge arrester of Type 2 category, developed for the protection function of low-voltage consumer installations against transient overvoltages. The manufacturer is DEHN, and the device carries the manufacturer's number 952405. It is specifically designed for use in the lightning protection zone concept, particularly at interfaces 0B – 1 and higher, where the risk of overvoltages due to direct or indirect lightning effects is highest. The device consists of a base unit into which protection modules are inserted, enabling a modular and adaptable protection configuration.
Applications
The surge arrester is intended for use in electrical installations in the low-voltage range, particularly in buildings with a TN-S network configuration. It protects sensitive consumer devices, such as electronic controls, heating systems, lighting systems, or IT infrastructure, from damage caused by overvoltages resulting from lightning strikes or network disturbances. The application typically takes place in a distribution box or near the main distribution, to secure the entire installation.
Functions and Equipment in Detail
The device operates on the principle of diverting overvoltages via a non-conductive state during normal operation and a conductive state during overvoltage. Surge arrester monitoring is performed using Thermo-Dynamic-Control technology, which continuously monitors the state of the arrester. In the event of damage or malfunction of the arrester, this is indicated by a visual or electrical signal, enabling timely maintenance or replacement. This monitoring increases device safety and prevents unintended failures or damage to downstream equipment.
Technology Explained Simply
The DEHNguard M TNS 275 FM is certified according to standard EN 61643-11, which applies to Type 2 surge arresters. Type 2 arresters are intended for use near the consumer installation and protect against overvoltages caused by indirect lightning effects or network disturbances. The designation TNS refers to the TN-S network configuration, in which the protective earth conductor (PE) and the neutral conductor (N) are separated in the distribution board. The device is designed for four poles, enabling complete protection for phase conductors and the neutral conductor in a TN-S installation. The modular design allows flexible adaptation to different installation configurations.
Compatibility and Accessories
For use with the DEHNguard M TNS 275 FM, accessory 943405 DG MD TNS 275 FM is available, a Type 2 surge arrester guard MD, also designed for TN-S networks. This accessory can be used to extend or supplement the protection function in more complex installations. The combination of both modules enables a detailed protection strategy, particularly in installations with multiple distribution boards or different loads.
Mounting and Installation
Installation takes place in a suitable distribution box or enclosure, with electrical connections to be made in accordance with VDE and EN standards. The modules are inserted into the base unit, ensuring correct pole assignment and maintaining minimum distances from other components. Installation should be carried out by a qualified electrician to ensure the safety and functionality of the system.
Advantages in Operation
The integrated surge arrester monitoring with Thermo-Dynamic-Control increases operational safety. The user receives clear feedback on the status of the arrester, helping to optimize maintenance intervals and avoid unexpected failures. The modular design enables flexible adaptation to different installation configurations, increasing the reusability and scalability of the system. Certification according to EN 61643-11 guarantees compliance with European safety and performance standards for Type 2 surge arresters.