| General |
| Degree of protection | Type 2 |
| Norm | EN 61643-11 |
| Monitoring technology | Thermo-Dynamik-Control |
| Number of poles | 4-pole |
| Use in lightning protection zone concept | interfaces 0B – 1 and higher |
| Arrester use at 16.7 Hz – traction power supply systems |
| Test voltage AC (UC) | 275 V |
| Nominal AC voltage (UN) | 230 / 400 V |
| Nominal frequency AC (fN) | 16.7 Hz |
| Standards |
| Certification | UL |
| UL Standard | UL 1449 5th edition |
| UL File Number | E319777 |
| Technical data |
| Energy coordination with terminal equipment (≤ 10 m) | type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 230 / 400 V (50 / 60 Hz) |
| Max. continuous operating voltage (a.c.) [L-N] (UC) | 275 V (50 / 60 Hz) |
| Max. continuous operating voltage (a.c.) [N-PE] (UC) | 255 V (50 / 60 Hz) |
| Nominal discharge current (8/20 µs) (In) | 20 kA |
| Max. discharge current (8/20 µs) (Imax) | 40 kA |
| Combination wave [L-N] (UOC) | 20 kV |
| Combination wave [N-PE] (UOC) | 6 kV |
| Voltage protection level [L-N]/[N-PE] (UP) | ≤ 1.5 / ≤ 1.5 kV |
| Voltage protection level [L-N]/[N-PE] at 5 kA (UP) | ≤ 1 / ≤ 1.5 kV |
| Protective conductor current (IPE) | ≤ 10 µA |
| Response time [L-N] (tA) | ≤ 25 ns |
| Response time [N-PE] (tA) | ≤ 100 ns |
| Max. mains-side overcurrent protection | 125 A gG |
| Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR) | 50 kArms |
| Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 335 V / 5 sec. – Festigkeit, 440 V / 120 min. – sicherer Ausfall |
| Temporary overvoltage (TOV) [N-PE] (UT) - Characteristic | 1200 V / 200 ms – withstand |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (min.) | 1.5 mm2 solid / flexible |
| Cross-sectional area (max.) | 35 mm2 stranded / 25 mm2 flexible |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IP 20 (integrated) |
| Capacity | 4 Standard DIN module, DIN 43880 |
| Approvals | DEKRA, VDE, UL |
| Type of remote signalling contact | changeover contact |
| Switching capacity (a.c.) | 250 V / 0.5 A |
| Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
| Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
| Test values according to UL 1449 |
| Rated Voltage (AC, 50/60 Hz) | 230 V |
| MCOV (AC, 50/60 Hz) [L-N]/[L-G]/[N-G] | 275 V |
| Voltage protection rating (VPR) | ≤ 1500 / ≤ 1500 V |
| Nominal discharge current (8/20µs) ( In) | 20 kA |
| Maximum ambient temperature | 85 °C |
| UL 1449 edition | 5th edition |
| Type (SPD classification) | Type 4 component assembly |
The DEHNguard M TT 275 FM is a multipole surge arrester of Type 2 category, designed for the protection of low-voltage consumer installations against transient overvoltages. The manufacturer is DEHN, and the device carries the manufacturer's number 952315. It is specifically designed for use in the lightning protection zone concept, particularly at interfaces 0B – 1 and higher, where it functions as the second protection stage to safeguard sensitive electrical equipment from damage caused by induced voltages or direct lightning strikes.
Applications
The arrester is intended for use in electrical installations with TT- and TN-S systems. It protects consumer installations in buildings that have earthing, and is particularly suitable for residential and commercial buildings where electrical devices such as heating systems, lighting, household appliances, or IT systems are connected. The application typically takes place in the distribution box, where it is installed between the supply line and the consumer system.
Functions and Equipment in Detail
The DEHNguard M TT 275 FM consists of a base unit and several plug-in protection modules, each covering one pole. The construction allows for modular expansion and maintenance. A central feature is the arrester monitoring with Thermo-Dynamic-Control, which continuously monitors the condition of the arrester. In case of a malfunction, for example due to thermal overload or wear, the arrester is automatically deactivated to prevent hazards from faulty discharge. This increases the safety of the entire installation.
Technology Explained Simply
The arrester operates on the principle of overvoltage limitation. When a voltage spike exceeds the permissible operating voltage range, it switches within nanoseconds and safely diverts the excess energy. The protection function is achieved through nonlinear resistors, which are highly resistive under normal voltage conditions but suddenly become low resistive under overvoltage conditions. The Thermo-Dynamic-Control monitors the temperature and electrical condition of the protection modules to enable early detection of defects.
Compatibility and Accessories
The device is designed for TT- and TN-S systems, which cover most modern electrical installations in Germany and Europe. As suitable accessories, the DEHNguard MD TT 275 FM (article number 943315) is offered, which serves as an additional type of protection module for similar applications. Combination with other DEHN protection modules is possible, provided the system requirements and protection levels match.
Mounting and Installation
Installation takes place in a distribution box, where the arrester is connected to the supply line. Mounting is done by plugging the protection modules into the base unit, which is screwed into the distribution box. The electrical connection is made via the designated terminal clamps. Installation must comply with applicable VDE and EN standards, ensuring correct earthing and maintaining minimum distances from other components.
Advantages in Operation
The integrated monitoring function with Thermo-Dynamic-Control increases the reliability of protection. The user receives a clear indication when the arrester is no longer functional, simplifying maintenance and inspection. The modular design allows flexible adaptation to different installation configurations. Compliance with standard EN 61643-11 ensures conformity with European requirements for surge protection devices.