| Standards |
| Certification | UL |
| UL Standard | UL 1449 5th edition |
| UL File Number | E319777 |
| Technical data |
| Energy coordination with terminal equipment (≤ 10 m) | type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 230 / 400 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 275 V (50 / 60 Hz) |
| Nominal discharge current (8/20 µs) (In) | 20 kA |
| Max. discharge current (8/20 µs) (Imax) | 40 kA |
| Voltage protection level (UP) | ≤ 1.5 kV |
| Voltage protection level at 5 kA (UP) | ≤ 1 kV |
| Response time (tA) | ≤ 25 ns |
| Max. mains-side overcurrent protection | 125 A gG |
| Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR) | 50 kArms |
| Temporary overvoltage (UT) – characteristic | 335 V / 5 sec. – Festigkeit, 440 V / 120 min. – sicherer Ausfall |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (min.) | 1.5 mm2 solid / flexible |
| Cross-sectional area (max.) | 35 mm2 stranded / 25 mm2 flexible |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IP 20 (integrated) |
| Capacity | 3 Standard DIN module, DIN 43880 |
| Approvals | DEKRA, VDE, UL |
| Type of remote signalling contact | changeover contact |
| Switching capacity (a.c.) | 250 V / 0.5 A |
| Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
| Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
| Test values according to UL 1449 |
| Rated Voltage (AC, 50/60 Hz) | 230 V |
| MCOV (AC, 50/60 Hz) [L-N]/[L-G]/[N-G] | 275 V |
| Voltage protection rating (VPR) | 1500 V |
| Nominal discharge current (8/20µs) ( In) | 20 kA |
| Maximum ambient temperature | 85 °C |
| UL 1449 edition | 5th edition |
| Type (SPD classification) | Type 4 component assembly |
The DEHN surge arrester type DG M TNC 275 FM is a multipole, modular surge arrester from the DEHNguard modular product family, specifically designed for use in TN-C systems. It protects low-voltage consumer installations against transient overvoltages caused by lightning strikes or network disturbances. The device is classified as Type 2 + Type 3 according to IEC 61643-11 / EN IEC 61643-11 and is suitable for use in the lightning protection zone concept at interfaces 0B - 1 and higher. The energy-coordinated protection effect within the Red/Line family ensures optimal coordination with downstream devices over a distance of up to 10 meters.
Applications
The arrester is intended for indoor use and is mounted on a 35 mm DIN rail in accordance with EN 60715. It is designed for low-voltage installations with a nominal voltage of 230/400 V (50/60 Hz) and has a maximum continuous voltage of 275 V AC. The overvoltage category (OVC) for the main circuit is III, allowing application near consumers or at the distribution level. The auxiliary circuit is equipped with OVC II, ensuring safe use of remote signaling contacts.
Functions and Equipment in Detail
The device consists of a base unit and plug-in protection modules that can be replaced without tools. Surge arrester monitoring is performed via the Thermo-Dynamic-Control system, which continuously monitors the arrester's condition. A green LED indicates proper functionality, while a red LED signals a fault. At the end of the arrester's service life, an open circuit (OCM) is achieved to ensure safe disconnection.
Technology Explained Simply
The arrester features high surge current handling capacity thanks to powerful zinc oxide varistors and spark gaps. The nominal surge current is 20 kA (8/20 µs), with a maximum surge current of 40 kA. The protection level is ≤ 1.5 kV; at a test current of 5 kA, it is ≤ 1 kV. The response time is ≤ 25 ns, enabling rapid reaction to overvoltages. The TOV voltage (UT) is specified as 335 V/5 sec. (withstand) and 440 V/120 min. (safe failure). The short-circuit withstand capability is 50 kAeff with a maximum network-side overcurrent protection of 125 A gG.
Compatibility and Accessories
The arrester is designed for use in TN-C systems and includes a potential-free remote signaling contact in changeover configuration. The switching capacity is 250 V / 0.5 A (AC) and 250 V / 0.1 A (DC), 125 V / 0.2 A (DC), 75 V / 0.5 A (DC). The connection cross-sections for main conductors range from 1.5 mm² (min.) to 35 mm² (max. stranded) or 25 mm² (max. fine-stranded). For FM terminals, the maximum connection cross-section is 1.5 mm² (single- or fine-stranded). The insulation between main and auxiliary circuits is double-insulated.
Mounting and Installation
Mounting is on a 35 mm DIN rail in accordance with EN 60715. The housing is made of a thermoplastic material in red, certified to UL 94 V-0. The installation dimensions correspond to 3 TE according to DIN 43880. The operating temperature range is between -40 °C and +80 °C. The protection rating is IP 20 (installed), providing protection against finger contact and solid foreign objects, but not against water or dust.
Operational Advantages
The modular design allows for easy replacement of protection modules without tools. The integrated fault indication and arrester monitoring increase safety and prevent unintended damage to downstream devices. The energy coordination within the Red/Line family ensures optimal alignment throughout the entire protection concept. Certifications from DEKRA, VDE, and UL confirm compliance with international safety standards.