Further information for DEHN 942440 surge arrester Type 2
General
SPD according to EN 61643-11 / IEC 61643-11
type 2 / class II
Energy coordination with terminal equipment (≤ 10 m)
type 2 + type 3
Nominal voltage (a.c.) (UN)
230 / 400 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.) [L-PE] (UC)
275 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.) [N-PE] (UC)
255 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In)
20 kA
Nominal load current for “V-connection” (IL)
40 A
Voltage protection level [L-PE]/[N-PE] (UP)
≤ 1.5 / ≤ 1.5 kV
Voltage protection level [L-PE]/[N-PE] at 5 kA (UP)
≤ 1.5 / ≤ 1.5 kV
Response time (tA)
≤ 100 ns
Short-circuit withstand capability (ISCCR)
25 kArms
Max. mains-side overcurrent protection with “V-connection”
40 A gG
Temporary overvoltage (UT) – characteristic
335 V / 5 sec. – withstand, 440 V / 120 min. – withstand
Leakage current
no leakage current
Operating temperature range (TU)
-40 °C ... +80 °C
Operating state / fault indication
green / red
Number of ports
1
Cross-sectional area (min.)
1.5 mm2 solid, 6 mm2 flexible
Cross-sectional area (max.)
10 mm2 solid / flexible
For mounting on
35 mm DIN rails acc. to EN 60715
Enclosure material
thermoplastic, red, UL 94 V-0
Place of installation
indoor installation
Degree of protection
IP 20
Capacity
4 Standard DIN module, DIN 43880
Approvals
KEMA, VDE
Type of remote signalling contact
changeover contact
Switching capacity (a.c.)
250 V / 0.5 A
Switching capacity (d.c.)
250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area for remote signalling terminals
max. 1.5 mm2 solid / flexible
Additional external fuse necessary
Multipole surge arrester DEHNguard MP ACI, type 2 according to EN 61643-11 with integrated ACI switch/spark gap combination, consisting of a base part with plugged-in protection modules and double push-in connection terminal suitable for branch and through-wiring. High device safety due to arrester monitoring with thermo-dynamic control. For protecting low-voltage consumer systems against surges. For use in the lightning protection zone concept at the interfaces 0B - 1 and higher.