| Extended technical data |
| Max. discharge current (8/20 µs) [1/2 - PG], [1+2 - PG] (Imax) | 20 kA |
| Discharge current (8/20 µs) [1/2 - PG], [1+2 - PG] | 10 kA (10x) |
| Voltage protection level line-PG at 1 kV/μs C3 after being subjected to Imax (UP) | ≤ 1000 V |
| Technical data |
| SPD class | L |
| Impulse category | D1, C1, C2, C3, B2 |
| Nominal voltage (UN) | 24 V |
| Max. continuous operating voltage DC (UC) | 36 V |
| Max. continuous operating a.c. voltage (UC) | 25.4 V |
| Nominal current at 80°C (IL) | 0.5 A |
| D1 Total lightning impulse current (10/350 µs) (Iimp) | 3 kA |
| D1 Lightning impulse current (10/350 µs) per line (Iimp) | 1.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In) | 10 kA |
| C2 Nominal discharge current (8/20 µs) per line (In) | 5 kA |
| Voltage protection level line-line for In C2 (UP) | ≤ 65 V |
| Voltage protection level line-PG for In C2 (UP) | ≤ 1100 V |
| Voltage protection level line-line at 1 kV/µs C3 (UP) | ≤ 48 V |
| Voltage protection level line-PG at 1 kV/µs C3 (Up) | ≤ 1000 V |
| Series resistance per line | 1 Ohm |
| Cut-off frequency line-line (fG) | 3.5 MHz |
| Capacitance line-line (C) | ≤ 2 nF |
| Capacitance line-PG (C) | ≤ 15 pF |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Degree of protection | IP 20 |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Connection (input / output) | push-in / push-in |
| Cross-sectional area, solid | 0.2-2.5 mm2 |
| Cross-sectional area, flexible | 0.2-2.5 mm2 |
| Earthing via | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | polyamide PA 6.6 |
| Colour | blue |
| Test standards | IEC 61643-21 / EN 61643-21 |
| Approvals | ATEX, IECEx, CCC, SIL |
| SIL classification | up to SIL3 *) |
| ATEX approvals (1) | TÜV 19 ATEX 8476 X: II (1)2 G Ex ia [ia Ga] IIC T4 ... T6 Gb |
| ATEX approvals (2) | TÜV 19 ATEX 8476 X: II 2 G Ex ib IIC T4 ... T6 Gb |
| ATEX approvals (3) | TÜV 19 ATEX 8476 X:II (1) D [Ex ia Da] IIIC |
| IECEx approvals (1) ( ) | IECEx TUR 20.0025X: Ex ia [ia Ga] IIC T4 ... T6 Gb |
| IECEx approvals (2) | IECEx TUR 20.0025X: Ex ib IIC T4 ... T6 Gb |
| China Compulsory Certification | CCC No. 2021312304001130 (Ex ia, Ex ib) |
Space-saving, compact surge arrester with a width of 6 mm and push-in connection technology with status display for protecting 1 double wire of intrinsically safe measuring circuits and bus systems. Meets FISCO requirements. Insulation strength >500 V wire-earth.