| Extended technical data |
| Discharge current (8/20 µs) [1/2 - PG], [1+2 - PG] | 10 kA (10x) |
| Voltage protection level line-PG at 1 kV/μs C3 after being subjected to Imax (UP) | ≤ 700 V |
| Technical data |
| SPD class | A |
| Impulse category | D1, C2, C3 |
| Nominal voltage (UN) | 180 V |
| Max. continuous operating voltage DC (UC) | 180 V |
| Max. continuous operating a.c. voltage (UC) | 127 V |
| Nominal current (IN) | 1.2 A |
| D1 Total lightning impulse current (10/350 µs) (Iimp) | 3 kA |
| D1 Lightning impulse current (10/350 µs) per line (Iimp) | 1.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In) | 10 kA |
| C2 Nominal discharge current (8/20 µs) per line (In) | 5 kA |
| Voltage protection level line-line for In C2 (UP) | ≤ 1100 V |
| Voltage protection level line-PG for In C2 (UP) | ≤ 800 V |
| Voltage protection level line-line at 1 kV/µs C3 (UP) | ≤ 950 V |
| Voltage protection level line-PG at 1 kV/µs C3 (Up) | ≤ 700 V |
| Series resistance per line | 0 Ohm |
| Cut-off frequency line-line at 100 ohms (fG) | 150 MHz |
| Capacitance line-line (C) | ≤ 10 pF |
| Capacitance line-PG (C) | ≤ 13 pF |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Degree of protection (with plugged-in protection module) | IP 20 |
| Pluggable into | BCO base part |
| Earthing via | BCO base part |
| Enclosure material | polyamide PA 6.6 |
| Colour | yellow |
| Test standards | IEC 61643-21 / EN 61643-21 |
| Approvals | UL 497B, CSA, ATEX, IECEx, CCC, SIL |
| SIL classification | up to SIL3 *) |
| ATEX approvals | TÜV 20 ATEX 8527 X: II 3G Ex ec IIC T4 Gc |
| IECEx approvals | IECEx TUR 20.0063X: Ex ec IIC T4 Gc |
| China Compulsory Certification | CCC no. 2021312304001192 |
Lightning current arrester protection module in 6 mm width for BLITZDUCTORconnect with status display to protect 2 individual wires for lightning protection equipotential bonding as well as the implementation of indirect earthing of shielded cables.