| General |
| SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
| Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 230 / 400 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 255 V (50 / 60 Hz) |
| Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal) | 50 kA |
| Lightning impulse current (10/350 µs) [L-N] (Iimp) | 12.5 kA |
| Specific energy [L-N] (W/R) | 39.06 kJ/Ohm |
| Lightning impulse current (10/350 µs) [N-PE] (Iimp) | 50 kA |
| Specific energy [N-PE] (W/R) | 625 kJ/Ohm |
| Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In) | 20 / 80 kA |
| Voltage protection level [L-N] (UP) | ≤ 1.5 kV |
| Voltage protection level [N-PE] (UP) | ≤ 1.5 kV |
| Open-circuit voltage of the combination wave generator (UOC) | 20 kV |
| Max. mains-side overcurrent protection | 160 A gG |
| Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
| Temporary overvoltage (TOV) [N-PE] (UT) - Characteristic | 1200 V / 200 ms – withstand |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (PEN, ) | 16-25 mm2 flexible / 16-35 mm2 stranded |
| For mounting on | 40 mm busbar systems |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IP 30 (in combination with cover) |
| Approvals | VDE |
| Power supply (for compartment for additional applications/termination point meter mounting board according to VDE-AR-N 4100) (UN) | 230 V |
| Extended technical data |
| Voltage protection level [L-PE] (UP) | ≤ 1.6 kV |
Combined arrester type 1 + type 2 + type 3 in accordance with EN 61643-11 for TT and TN-S systems (3+1 circuit) with 230 V power supply (N and L) each for RfZ / APZ in accordance with VDE-AR-N 4100. Including a single-pole B6 circuit breaker for the power supply of the intelligent measuring system in accordance with VDE-AR-N 4100, with sealable protective cover, for use on the 40 mm busbar system in the main power supply system in accordance with DIN VDE 0100-443 in buildings with an external lightning protection system (lightning protection class III/IV). 2 x socket and 2 x plug for easy wiring of the intelligent measuring system are included in the scope of delivery.