| General |
| SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
| Tested to | EN 61439-1 / ... IEC 61439-1, EN 61439-2 / ... IEC 61439-2 |
| Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 230 / 400 V (50 / 60 Hz) |
| Max. continuous operating voltage (a.c.) [L-N]/[N-PE] (UC) | 255 V (50 / 60 Hz) |
| Nominal alternating current (IL) | 32 A |
| Max. power | 11 / 22 kW |
| Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp) | 12.5 / 50 kA |
| Specific energy [L-N]/[N-PE] (W/R) | 39.06 kJ/ohms / 625.00 kJ/ohms |
| Nominal discharge current (8/20 µs) (In) | 25 / 100 kA |
| Voltage protection level [L-N] (UP) | ≤ 1.5 kV |
| Voltage protection level [N-PE] (UP) | ≤ 1.5 kV |
| Follow current extinguishing capability [L-N]/[N-PE] (Ifi) | 25 kArms / 100 Arms |
| Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
| Response time (tA) | ≤ 100 ns |
| Max. backup fuse (L) up to IK ≤ 25 kArms | 40 A gG |
| Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
| Temporary overvoltage (TOV) [N-PE] (UT) - Characteristic | 1200 V / 200 ms – withstand |
| Operating temperature range [parallel]/[series] (TU) | -40°C...+80°C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (L1, L2, L3, N, PE, ) (min.) | 0,5 mm2 |
| Cross-sectional area (L1, L2, L3, N, PE, ) (max.) | 16 mm2 |
| Type of remote signalling contact | changeover contact |
| Switching capacity (a.c.) | 250 V / 0.5 A |
| Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
| Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
| Place of installation | Installation in protected outdoor areas |
| Degree of protection | IP 65 |
| Type | with pressure compensating element |
| Cover | Transparent cover with product label |
| Enclosure colour | grey |
| Input | Ölflex 5x 6 mm², length 1.5 m |
| Output | System-side connection with M25 screw connection |
| Enclosure dimensions (W x H x D) | 217 x 253 x 115 mm |
Housing connection box DCU EMOB 1 32, type 1 + type 2, with protection class IP 65, according to DIN EN IEC 61643-11 and 61439-2, for universal installation in front of the wallbox.