| General |
| SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
| Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 230 / 400 V (50 / 60 Hz) |
| Max. continuous operating voltage (a.c.) [L-N]/[N-PE] (UC) | 255 V (50 / 60 Hz) |
| Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp) | 12.5 / 50 kA |
| Specific energy [L-N]/[N-PE] (W/R) | 39.06 kJ/ohms / 625.00 kJ/ohms |
| Nominal discharge current (8/20 µs) (In) | 25 / 100 kA |
| Voltage protection level [L-N]/[N-PE] (UP) | ≤ 1.5 kV / ≤ 1.5 kV |
| Follow current extinguishing capability [L-N]/[N-PE] (Ifi) | 25 kArms / 100 Arms |
| Follow current limitation / Selectivity | No tripping of a 35 A gG fuse up to 25 kArms (prosp.) |
| Response time (tA) | ≤ 100 ns |
| Max. backup fuse (L) up to IK ≤ 25 kArms | 250 A gG |
| Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
| Temporary overvoltage (TOV) [N-PE] (UT) - Characteristic | 1200 V / 200 ms – withstand |
| Operating temperature range [parallel]/[series] (TU) | -40°C...+80°C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (L1, L2, L3, N, PE, ) (min.) | 1.5 mm2 solid / flexible |
| Cross-sectional area (L1, L2, L3, N, PE, ) (max.) | 35 mm2 stranded / 25 mm2 flexible |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IP 20 |
| Capacity | 4 Standard DIN module, DIN 43880 |
| Approvals | KEMA, UL |
| Type of remote signalling contact | changeover contact |
| Switching capacity (a.c.) | 250 V / 0.5 A |
| Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
| Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
| Insulation measurement possible when connected | up to 1000 V DC |
| Extended technical data |
| Additional abnormal voltage test: 485 V AC / 50 Hz for 24 h | withstand |
| Residual energy with a S20K275 | < 0.5 J |
| characteristic at U = 320 V and ISCCR = 13.5 kA with fuse 63 A gG | withstand |
| Voltage protection level [L-PE] (UP) | ≤ 2.0 kV |
¦ Universally applicable combination arrester, especially for use in power supply systems for charging infrastructure
¦ Based on spark gap technology with only 1 HP / pole enables compact and space-saving installation
¦ Energy-coordinated protective effect for the type 1 + type 2 end device + Type 3