| Technical data |
| Series | eLLK 92 |
| Design | Surface-mounted luminaire |
| Lamp | 2 x T26 / 18 W (T8) |
| Lamp base | G13 (IEC 60061-1) |
| Rated lamp luminous flux | 2700 lm (lamp-dependent) |
| Light output ratio | 78 % |
| Circuit | Electronic ballast, dual-channel with EOL monitoring |
| Rated voltage | 110 - 254 V AC / 110 - 250 V DC |
| Rated current | 0.18 A |
| Frequency | 50 - 60 Hz |
| Power factor | ≥ 0.95 |
| Protection class | I |
| Degree of protection | IP66 (EN 60529) |
| Impact resistance | IK10 (20 J) to IEC/EN 62262 |
| Ex zones | 1, 2, 21, 22 |
| Marking to 2014/34/EU | II 2G Ex db eb IIC T4 Gb; II 2D Ex tb IIIC T80 °C Db |
| IECEx marking | Ex de IIC T4 Gb; Ex tb IIIC T80 °C Db |
| EC type examination certificate | BVS 09 ATEX E 034 |
| IECEx certificate | IECEx BVS 09.0033 |
| Ambient temperature | -25 °C to +55 °C (UN ≥ 220 V), -25 °C to +50 °C (UN ≤ 220 V) |
| Surge immunity | 4 kV, L - N and L - PE (EN 61000-4-5) |
| Terminals | 2 x 6; L1, L2, L3, L, N, PE; max. 2 x 6 mm² solid per terminal |
| Through-wiring | both sides |
| Cable entry | 2 x M25, Ex e cable gland M25 x 1.5 plastic |
| Screw plug | 2 x M25 |
| Dimensions (L x W x H) | 760 x 188 x 130 mm |
| Weight | 5.2 kg |
| Housing material | Glass-fibre reinforced polyester |
| Housing colour | RAL 7035 light grey |
| Protective cover | Polycarbonate |
| Scope of delivery | without lamps and fixing material |
Ex luminaire for fluorescent lamps for zone 1/21, eLLK 92018/18 (2 x 18 W), 2/6-2K, cable entries: 2 x M25, plastic, standard two-channel electronic ballast with EOL monitoring, fluorescent lamp T8, lamp base: G13 in accordance with IEC 60061, two-sided through-wiring: yes, cable entries/housing holes: 2 x Ex-e cable entries M25 x 1.5 (plastic) for Ø 8 - 17 mm, 2 x Ex-e screw cap, housing material: glass fiber reinforced polyester, protective hood/protective cover: polycarbonate, frequency: 50 - 60 Hz, rated current: 0.18 A, marking according to 94/9/EC: Ex II 2 G Ex de IIC T4 Gb, Ex II 2 D Ex tb IIIC T80 °C Db IP66, EC type examination certificate: BVS 09 ATEX E 034, Permissible ambient temperature: -25 °C to 55 °C, Weight: 5.49 kg, Protection class: I, Protection type according to EN 60529: IP66