| Certificates |
| Compliance certificates | CE, UKCA |
| Design |
| PDU types | Switched |
| Type | Single-phase |
| Rack capacity | 0U |
| Mounting | Vertical |
| Product colour | Black |
| Logistics data |
| Total carbon footprint (kg of CO2e) | 1088 |
| Operational conditions |
| Operating temperature (T-T) | -5 - 50 °C |
| Storage temperature (T-T) | -25 - 65 °C |
| Operating relative humidity (H-H) | 5 - 95% |
| Storage relative humidity (H-H) | 5 - 95% |
| Operating altitude | 0 - 3000 m |
| Packaging data |
| Package weight | 7.6 kg |
| Package width | 170 mm |
| Package depth | 1810 mm |
| Package height | 1260 mm |
| Ports & interfaces |
| AC outlets quantity | 24 AC outlet(s) |
| Power plug | IEC 60309 |
| AC outlet types | C13 coupler |
| Power |
| Nominal input voltage | 230 V |
| AC input frequency | 50/60 Hz |
| Maximum current | 16 A |
| Nominal output voltage | 230 V |
| Output voltage | 230 V |
| Load capacity | 3680 VA |
| Number of phases | 1 |
| Weight & dimensions |
| Width | 56 mm |
| Depth | 62 mm |
| Height | 1650 mm |
| Weight | 6.1 kg |
The APC Easy PDU Switched Null HE 16A 230V (20)C13 (4)C19 IEC309, type EPDU2116S, is a rack-mountable power distribution unit (PDU) for use in IT and server environments. It serves for the efficient distribution and control of electrical power to multiple devices within a rack. The unit is designed as a
0U module, meaning it does not occupy any vertical rack unit space and thus saves space within the rack. Installation is carried out
vertically on the rack wall, using integrated mounting brackets or included holders. The device is
black in colour, enabling discreet integration into standard rack environments.
Applications
The PDU is designed for use in server rooms, data centres, and IT infrastructures where reliable and controllable power supply to multiple end devices is required. Due to its vertical mounting and narrow width of 56 mm, it is particularly suitable for racks with limited space. The unit is intended for
indoor use and must not be installed in environments with increased humidity or heat. The operating temperature range is between -5 °C and 50 °C, and the storage temperature range is between -25 °C and 65 °C.
Functions and Equipment in Detail
The PDU features a total of
24 AC outlets, with 20 outlets equipped with
C13 connectors (IEC 60320) and 4 outlets with
C19 connectors (IEC 60320). These connector types are standard in IT and server equipment. The input is fitted with an
IEC 60309 plug 16 A 2-pole + E, which connects to a 230 V socket. The maximum current is
16 A, and the nominal voltage at both input and output is
230 V. The total power (load capacity) is
3680 VA, equivalent to a load of up to 3.68 kW. The PDU is designed for
single-phase supply.
Technology Explained Simply
The PDU enables
controllable power distribution – individual outlets can be switched on and off via a network management interface (Web, SNMP, CLI). This supports load optimisation, prevents overloads, and allows targeted power delivery to specific devices. Control is performed via an IP address, enabling remote management and monitoring. Firmware can be updated over the network, avoiding hardware replacement in the field. The PDU displays
overload and warning conditions based on user-defined alarm thresholds. Power delivery to individual outlets can be controlled sequentially to coordinate startup processes and avoid inrush currents.
Compatibility and Accessories
The PDU is equipped with an
IEC 60309 plug 16 A, which connects to a corresponding socket. The outlets are fitted with C13 and C19 connectors, compatible with most IT and server devices. Installation is vertical within the rack, using either integrated mounting brackets or included holders. The packaging includes an
installation manual. The PDU is designed for use in racks with standard 19-inch construction.
t
Installation and Mounting
Mounting is performed vertically on the rack wall. The unit can be secured using either the integrated mounting brackets or included holders. Installation requires no tools when using the mounting brackets. When using holders, M3 x 12 screws and M5 x 10 mm self-tapping screws are required. The input plug must be connected to a
grounded socket. The PDU must not be installed in environments with increased humidity or heat. Installation must be carried out by a qualified person.
Operational Advantages
Vertical mounting and the 0U form factor save valuable space within the rack. Controllable outlets enable intelligent load distribution and monitoring. Remote management via network protocols (Web, SNMP, CLI) simplifies maintenance and configuration. Network-based firmware updates reduce maintenance effort. Sequential power delivery prevents inrush currents and supports proper startup of dependent devices. Display of warning and error conditions supports proactive operation.
Certifications and Environment
The PDU is certified with
CE and
UKCA conformity marks. The operating altitude is up to 3000 m above sea level. The relative humidity during operation is between 5 % and 95 %, without condensation. The environmental impact (CO2 footprint) is 1088 kg CO2e. The product is compliant with the EU RoHS Directive, with exceptions. Disposal must comply with the WEEE Directive – the device must not be disposed of as household waste.
The PDU is designed for use in IT infrastructures where reliable, controllable, and monitorable power supply is required. The combination of space-saving, remote control, and load monitoring makes it a suitable solution for modern data centres and server rooms.