| Certificates |
| Compliance certificates | RoHS |
| Certification | EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3, VDE |
| Design |
| PDU types | Metered, Metered-by-outlet, Switched |
| Type | Single-phase |
| Rack capacity | 0U |
| Mounting | Vertical |
| Product colour | Black |
| Features |
| Cable length | 3 m |
| Logistics data |
| Total carbon footprint (kg of CO2e) | 8595.81 |
| Management features |
| Monitoring | Current, Power, Voltage |
| Outlet control | Lock-out, Recycle, Turn off, Turn on |
| Operational conditions |
| Operating temperature (T-T) | -5 - 45 °C |
| Storage temperature (T-T) | -25 - 65 °C |
| Operating relative humidity (H-H) | 5 - 95% |
| Storage relative humidity (H-H) | 5 - 95% |
| Operating altitude | 0 - 3000 m |
| Non-operating altitude | 0 - 15000 m |
| Packaging data |
| Package weight | 10.5 kg |
| Package width | 162 mm |
| Package depth | 118 mm |
| Package height | 2038 mm |
| Ports & interfaces |
| AC outlets quantity | 24 AC outlet(s) |
| Power plug | IEC309 |
| AC outlet types | C13 coupler, C19 coupler |
| Power |
| Nominal input voltage | 230 V |
| AC input frequency | 50 - 60 Hz |
| Maximum current | 32 A |
| Nominal output voltage | 230 V |
| Load capacity | 7680 VA |
| Maximum input current per phase | 32 A |
| Maximum total current draw per phase | 32 A |
| Power protection features | Overload |
| Maximum power | 7680 W |
| Weight & dimensions |
| Width | 56 mm |
| Depth | 51 mm |
| Height | 1829 mm |
| Weight | 8.23 kg |
APC Metered by Outlet with Switched Rack PDUs provide comprehensive, user-customizable control of power distribution with individually switchable outlets and power metering. Individual outlets can be remotely turned on and off to restart systems or prevent unauthorized use of outlets. Delayed power-on sequences can be used to specify the switching sequence of connected systems. Load shedding prioritization can be used to optimize circuit overloads and the power-on and resilience of critical systems. Metering functions enable real-time remote monitoring of connected loads. Switched Rack PDUs feature real-time power monitoring, a temperature/humidity sensor port, and lockable IEC ports. User-definable alarms warn of potential overloads before failures occur. Switched Rack PDUs are configured and controlled via web, SNMP, or Telnet interfaces. Integration with APC Centralized Management Platforms is also possible, such as: E.g. in InfraStruxure Central, Capacity Manager and Change Manager.