The ABB surge protection device OVR T2 3L 40-350 P QS is a protection device of type class 2 (SPD Type 2) for use in electrical installations with network configuration TN and TN-C. It provides protection against indirect lightning effects as well as switching overvoltages and is installed as close as possible to the supply point of the installation. The device consists of a base unit and a replaceable protection module, ensuring simple maintenance and replaceability. The protection device is designed for use in sub-distribution boards and final circuits and offers a protection level of 1.5 kV (L-N), enabling effective shielding against overvoltages in the nominal voltage range of 230 V AC.
Applications
The OVR T2 3L 40-350 P QS is designed for use in electrical installations with a network configuration TN or TN-C. It protects installations in buildings operated via a distribution switchboard with 3 conductors (without earth). The maximum continuous voltage is 350 V AC, enabling use in standard voltage installations with 230/400 V. The device is suitable for indoor use, as it features protection class IP20, which provides protection against contact with fingers and against solid foreign objects up to 12.5 mm in diameter.
Functions and Equipment in Detail
The device features a mechanical function indicator that optically signals the operating status. This indicator allows visual inspection of functionality without additional measuring instruments. The integrated thermal monitoring QuickSafe® ensures continuous monitoring of internal temperature and reacts to overheating to prevent damage to the device or the installation. The protection device is equipped with a nominal discharge current of 20 kA (8/20 µs), ensuring high shielding performance against short-term overvoltages. The short-circuit withstand capability is 100 kA, increasing safety in the event of a short circuit in the network.
Technology Explained Simply
The protection level of 1.5 kV (L-N) means that the device diverts overvoltages up to this value to protect sensitive consumers in the installation. The maximum discharge capacity of 20 kA (8/20 µs) corresponds to a high protection standard, sufficient for typical overvoltage events in industrial and building applications. The module size of 3 TE enables compact mounting in standard switchboards. The maximum permissible conductor cross-sections are 25 mm² for rigid (single- or multi-strand) and 16 mm² for flexible (fine-stranded) conductors, allowing flexible adaptation to various installation situations.
Compatibility and Accessories
The OVR T2 3L 40-350 P QS is compatible with the System pro M compact series and can be mounted on phase rails. This enables modular expansion of the distribution switchboard and easy integration into existing systems. The device is not equipped with a remote signaling contact but features optical signaling to visually indicate the operating status. An integrated fuse is not present.
Mounting and Installation
Mounting is carried out in standard switchboards, where the module size of 3 TE enables compact placement. The device is designed for indoor mounting and requires no special environmental conditions beyond the IP20 protection class. Installation should be carried out as close as possible to the supply point of the electrical installation to maximize protective effect. Wiring is done via the designated connection points, with maximum conductor cross-sections of 25 mm² (rigid) and 16 mm² (flexible) not to be exceeded.
Operational Advantages
The combination of mechanical function indicator and thermal monitoring QuickSafe® enables reliable monitoring of the operating status. The high short-circuit withstand capability of 100 kA increases safety in the event of a fault. The modular design with a replaceable protection module reduces maintenance effort and enables quick replacement in case of failure. Compatibility with the System pro M compact series facilitates integration into existing distribution systems.
Protection Class and Operating Conditions
The protection class IP20 safeguards the device against contact with fingers and against solid foreign objects up to 12.5 mm in diameter. The device is designed for indoor use and is not suitable for outdoor applications.