The ABB surge protection device OVR T2 40-275 C QS is a protection device of test class Type 2, specifically designed for use in electrical installations to protect against indirect lightning effects and switching surges. The device is installed close to the supply point of the installation to ensure effective protection of downstream consumers and wiring. It consists of a base unit and a replaceable protection module, ensuring simple maintenance and replaceability. The protection device is equipped with a mechanical function indicator that visually signals the operating status. The thermal monitoring QuickSafe® ensures reliable monitoring of internal temperature and supports the safety of the device. The unit is designed for TN and TN-C-S network configurations, making it suitable for typical low-voltage installations in buildings.
Applications
The OVR T2 40-275 C QS is primarily used in sub-distribution boards and final circuits. It is designed for protection functions in electrical installations connected to the public supply network. Installation should be carried out as close as possible to the supply point to optimally ensure protection for downstream devices and wiring. The protection device is designed for installations operating at a nominal voltage of 230 V AC, with a maximum continuous voltage of 275 V AC. The unit is intended for indoor use, as it has protection class IP20, which protects against contact with moving parts and against solid foreign objects larger than 12.5 mm.
Functions and Equipment in Detail
The device has a nominal discharge current of 20 kA (8/20 µs), defining the maximum energy absorption during surge events. The protection level is 1.25 kV, both for line-to-line connection (L-N) and neutral-to-earth (N-PE). These values ensure effective protection of connected devices. The short-circuit withstand capability (Isccr) is 100 kA, describing the device’s ability to withstand a short-circuit in the network without failure or hazard. The maximum conductor cross-section is 25 mm² for rigid conductors (single- or multi-strand) and 16 mm² for flexible, fine-stranded conductors. The protection device is not equipped with an integrated pre-fuse or remote signaling contact.
Technology Explained Simply
The OVR T2 40-275 C QS operates on the principle of surge limitation. When a surge exceeds the protection level of 1.25 kV, the device diverts the excess energy through the protection module to protect downstream devices. The thermal monitoring QuickSafe® monitors the internal temperature of the module and ensures the device safely shuts off in case of overheating. The mechanical function indicator allows visual inspection of the operating status without requiring additional measuring instruments. The mounting size is 4 TE, enabling installation in standard switchboards. Mounting is done via phase rails, and compatibility with the System pro M compact series is provided.
Compatibility and Accessories
The protection device is compatible with the System pro M compact series and can be mounted on phase rails. This enables flexible integration into existing switchgear installations. The replaceable protection module can be replaced as needed without replacing the entire device. The use of replacement modules reduces maintenance costs and increases the lifespan of the installation.
Mounting and Installation
Mounting is carried out in switchboards or sub-distribution units, with the unit secured via phase rails. Installation should position the device as close as possible to the supply point of the installation to optimally utilize the protection function. Wiring is done with conductors whose cross-section does not exceed the maximum values of 25 mm² (rigid) or 16 mm² (flexible). The unit is designed for TN and TN-C-S network configurations, enabling use in typical low-voltage installations. The IP20 protection class requires indoor installation, as there is no protection against water or dust.
Operational Advantages
The OVR T2 40-275 C QS provides reliable protection against surges caused by indirect lightning effects or switching operations. The mechanical function indicator enables quick visual inspection of the operating status. The thermal monitoring QuickSafe® enhances safety by detecting overheating and shutting off the device in case of danger. The replaceability of the protection module reduces maintenance costs and allows for quick repair without replacing the entire device. Compatibility with the System pro M compact series simplifies integration into existing installations. The unit is designed for a nominal voltage of 230 V AC, making it suitable for most industrial and commercial applications.