Further information for ABB Automation 2CSR772199R1164 circuit breaker DS202CR M C16 A30 110V
General
Number of poles (total)
2
Number of protected poles
2
Rated voltage
110
Rated insulation voltage Ui
440
Rated impulse withstand voltage Uimp
4
Rated current
16
Rated fault current
0.03
Leakage current type
A
Current limiting class
3
Rated short-circuit breaking capacity acc. EN 61009
10
Rated short-circuit breaking capacity IEC 60947-2
10
Rated short-circuit breaking capacity Icn acc. EN 61009-1
10
Disconnection characteristic
Undelayed
Surge current capacity
0.25
Voltage type
AC
Frequency
Other
Release characteristic
C
Over voltage category
3
Pollution degree
3
Ambient temperature during operating
55
Width in number of modular spacings
2
Built-in depth
72
Degree of protection (IP)
IP20
Connectable conductor cross section multi-wired
25
Mounting method
DIN rail
Power loss
4.2
Concurrently switching N-neutral
With interlocking device
Anti-nuisance tripping version
Residual current circuit breakers (RCBOs) offer protection for people and property, as well as protection against electrically ignited fires in accordance with DIN VDE 0100-410 and DIN VDE 0100-530. They guarantee protection of single-phase circuits against overload and short-circuit currents, protection against sinusoidal alternating currents and pulsating currents with a smooth DC residual current component of up to 6 mA to earth. As well as fault protection (protection against indirect contact), additional protection (with I¿n = 30 mA) and fire protection (with I¿n = 300 mA).
They meet the product standards IEC 61009-1, IEC 61009-2-1.
Areas of application are industrial and marine applications. The extensive range of accessories offers you everything you need for your installation tasks.
The DS202CR MA 110 V series does not have VDE approval and is specifically designed for 110 V AC applications, thanks to the test button voltage of 93 - 135 V AC. Numerous approvals make the DS202CR suitable for worldwide use.
For 50/60 Hz networks with 2 phases 110 V AC (without N conductor) or mobile distributors supplied via Schuko plug (1P+N).
Rated switching capacity according to IEC 61009 Icn = 10 kA.
RCBO DS202CR MA Type A is 2-pole protected (LS), 2-pole switching.