Further information for ABB Automation 2CSR275180R2405 FI/LS switch 1P+N B 40A
General
Number of poles (total)
2
Number of protected poles
1
Rated voltage
240
Rated insulation voltage Ui
500
Rated impulse withstand voltage Uimp
4
Rated current
40
Rated fault current
0.1
Leakage current type
A
Current limiting class
3
Rated short-circuit breaking capacity acc. EN 61009
10
Rated short-circuit breaking capacity IEC 60947-2
15
Rated short-circuit breaking capacity Icn acc. EN 61009-1
10
Disconnection characteristic
Undelayed
Voltage type
AC
Frequency
Other
Release characteristic
B
Over voltage category
3
Pollution degree
2
Ambient temperature during operating
55
Width in number of modular spacings
2
Built-in depth
69
Degree of protection (IP)
IP20
Connectable conductor cross section multi-wired
16
Mounting method
DIN rail
Power loss
9.1
Concurrently switching N-neutral
With interlocking device
Anti-nuisance tripping version
Residual current circuit breakers (RCBOs) offer protection for people and property, as well as protection against electrically ignited fires in accordance with DIN VDE 0100-410 and DIN VDE 0100-530. They guarantee protection of single-phase circuits against overload and short-circuit currents, protection against sinusoidal alternating currents and pulsating currents with a smooth DC residual current component of up
to 6 mA to earth. As well as fault protection (protection against indirect contact), additional protection (with I¿n = 30 mA) and fire protection (with I¿n = 300 mA). They meet the product standards IEC/EN 61009-1 (VDE 0664-20), IEC/EN 61009-2-1 (VDE 0664-21).
Areas of application include household, commercial and industrial applications. The extensive range of accessories offers you everything you need for your installation tasks. Numerous approvals make the DS201 suitable for worldwide use.
Rated switching capacity according to IEC/EN 61009 Icn = 10 kA.
RCBO DS201 MA Type A is 1-pole protected (LS), 2-pole switching.