| General |
| Number of poles (total) | 2 |
| Number of protected poles | 1 |
| Rated voltage | 240 |
| Rated insulation voltage Ui | 500 |
| Rated impulse withstand voltage Uimp | 4 |
| Rated current | 16 |
| Rated fault current | 0.03 |
| Leakage current type | A |
| Current limiting class | 3 |
| Rated short-circuit breaking capacity acc. EN 61009 | 6 |
| Rated short-circuit breaking capacity IEC 60947-2 | 6 |
| Rated short-circuit breaking capacity Icn acc. EN 61009-1 | 6 |
| Disconnection characteristic | Undelayed |
| Voltage type | AC |
| Frequency | Other |
| Release characteristic | B |
| Over voltage category | 3 |
| Pollution degree | 2 |
| Ambient temperature during operating | 55 |
| Width in number of modular spacings | 2 |
| Built-in depth | 69 |
| Degree of protection (IP) | IP20 |
| Connectable conductor cross section solid-core | 25 |
| Connectable conductor cross section multi-wired | 25 |
| Mounting method | DIN rail |
| Power loss | 4.5 |
Residual current circuit breakers (RCBOs) provide personal and material protection as well as protection against electrically ignited fires. They ensure protection of single-phase circuits against overload and short-circuit currents, protection against sinusoidal alternating currents and pulsating currents with a smooth DC residual current component of up to 6 mA to earth. As well as fault protection (protection against indirect contact), additional protection and fire protection.
Areas of application include household, commercial and industrial applications. The extensive range of accessories offers you everything you need for your installation tasks. The RCBO DS201 UL is mechanically compatible with the accessories, but both together are not UL approved.
This special series is UL (USA) and CSA (Canada) certified: UL 1053, UL 1077, CSA C22.2 N0. 144, CSA C22.2 N0. 235.
Rated switching capacity according to IEC/EN 61009 Icn = 6 kA.
RCBO DS201 A UL Type A is 1-pole protected (LS), 2-pole switching.