Further information for ABB Automation 2CSR255180R2164 FI/LS switch 1P+N
General
Number of poles (total)
2
Number of protected poles
1
Rated voltage
240
Rated insulation voltage Ui
500
Rated impulse withstand voltage Uimp
4
Rated current
16
Rated fault current
0.1
Leakage current type
A
Current limiting class
3
Rated short-circuit breaking capacity acc. EN 61009
6
Rated short-circuit breaking capacity IEC 60947-2
10
Rated short-circuit breaking capacity Icn acc. EN 61009-1
6
Disconnection characteristic
Undelayed
Voltage type
AC
Frequency
Other
Release characteristic
C
Over voltage category
3
Pollution degree
2
Ambient temperature during operating
55
Width in number of modular spacings
2
Built-in depth
69
Degree of protection (IP)
IP20
Connectable conductor cross section multi-wired
16
Mounting method
DIN rail
Power loss
4.5
Concurrently switching N-neutral
With interlocking device
Anti-nuisance tripping version
The ABB DS201 C16 A100 is a FI/LS-switch (also referred to as RCBO), designed for use in single-phase circuits. It combines the functions of a circuit breaker (LS) and a residual current device (FI) in one unit. This provides protection against overload and short circuit as well as dangerous earth fault currents that may arise from indirect contact. The device is suitable for use in residential, commercial, and industrial applications and complies with product standards IEC/EN 61009-1 (VDE 0664-20) and IEC/EN 61009-2-1 (VDE 0664-21). It ensures personal and property protection as well as fire protection in accordance with DIN VDE 0100-410 and DIN VDE 0100-530.
Applications
The DS201 C16 A100 is designed for use in electrical installations where combined protection against electrical hazards is required. It is particularly suitable for applications where protection against overload and short circuit as well as protection against earth fault currents is necessary. Compliance with standards enables use in various countries and industries. The protection functions include fault protection (protection against indirect contact), additional protection (at a fault current of 30 mA), and fire protection (at a fault current of 300 mA). These protection functions are designed for sinusoidal alternating currents as well as for pulsating currents with a smooth direct fault current component up to 6 mA to earth.
Functions and Equipment in Detail
The device is single-pole protected (LS), meaning protection against overload and short circuit occurs on one pole. It is two-pole switching, meaning it switches both the live and neutral conductors. The trip characteristic C ensures sufficiently fast disconnection in case of overload without unnecessary tripping due to short-term current surges. The rated residual current is 0.1 A (100 mA), which is sufficient for protection against dangerous earth fault currents. The rated voltage is 240 V, and the rated insulation voltage Ui is 500 V. The rated impulse withstand voltage Uimp is 4 kV, ensuring high stability against transient voltage surges. The energy limitation class 3 indicates that the device is capable of effectively limiting the energy of a short circuit.
Technology Explained Simply
The DS201 C16 A100 operates with an instantaneous trip characteristic, meaning it disconnects immediately upon reaching the threshold value. The rated breaking capacity is 6 kA according to EN 61009 and 10 kA according to IEC 60947-2. The rated short-circuit breaking capacity Icn is 6 kA according to EN 61009-1, describing the device’s ability to safely disconnect short-circuit currents up to this level. The overvoltage category 3 and pollution degree 2 indicate intended use in indoor environments where no extreme environmental conditions exist. The operating ambient temperature is up to 55 °C, enabling use in normal indoor environments. The protection rating IP20 protects against finger contact and solid foreign objects, but is not suitable for outdoor use.
Compatibility and Accessories
The device is designed for mounting on a DIN rail, enabling easy installation in standard switchboards. The installation depth is 69 mm, and the width corresponds to 2 module units, facilitating placement in standard switchboards. The connectable conductor cross-sections for multi-strand conductors are up to 16 mm². Various auxiliary switches are available as accessories, including the S2C-S/H6R auxiliary switch 1 changeover for LS and FI and the LS S2C-H6-11R auxiliary switch, which can be used to extend control and signaling functions. The power loss is 4.5 W, describing the heat generation during operation.
Mounting and Installation
Mounting is done on a DIN rail, enabling standardized and secure fastening in electrical switchboards. The installation dimensions are designed to allow easy integration into standard switchboards. Connection options for multi-strand conductors up to 16 mm² allow use with common installation cables. The locking device is not present, meaning the device cannot be mechanically locked.
Advantages in Operation
The DS201 C16 A100 offers compact and reliable protection in a single unit. The combination of LS and FI functions reduces the number of components required in the switchboard. The high breaking capacity of 6 kA according to EN 61009-1 ensures safe disconnection in case of short circuit. The trip characteristic C ensures balanced response to overloads. The protection functions in accordance with DIN VDE 0100-410 and DIN VDE 0100-530 meet requirements for protection against electrical hazards in various application areas. Use in residential, commercial, and industrial installations is enabled by standards compliance and worldwide approval.