Further information for ABB 2CSF204592R4630 RCD 4P 63A 500mA
General
Number of poles
4
Rated current
63
Rated impulse withstand voltage Uimp
4
Mounting method
DIN rail
Leakage current type
B
Surge current capacity
3
Frequency
50/60 Hz
Degree of protection (IP)
IP20
Width in number of modular spacings
4
Built-in depth
69
Ambient temperature during operating
50
Pollution degree
3
Connectable conductor cross section multi-wired
25
Connectable conductor cross section solid-core
25
Depth of device
69
Height of device
85
RAL-number (akin)
7035
Width of device
70
Selective protection
Short-time delayed tripping
Additional equipment possible
With interlocking device
Explosion-proof
The residual current circuit breaker F204 B-63/0.5 from ABB is a 4-pole, short-time delayed circuit breaker for use in electrical installations. It is designed for a rated current of 63 A and detects residual currents from 500 mA. The breaker is designed for mounting on a DIN rail and corresponds to protection type B, which is specifically suitable for installations with non-linear loads such as frequency converters or electronic equipment. It is universal current sensitive and detects residual currents in the frequency range of 0 to 2 kHz, including smooth direct residual currents, pulsating currents, and sinusoidal alternating currents. The rated impulse voltage withstand is 4 kV, and the impulse current withstand is 3 kA, making it suitable for use in installations with high transient currents. The protection class IP20 safeguards against finger contact and against solid foreign objects, assuming a pollution degree of 3. The operating ambient temperature must not exceed 50 °C.
Applications
This circuit breaker is intended for use in household, commercial, and industrial installations. It provides personal and property protection as well as fire protection in accordance with DIN VDE 0100-410 and DIN VDE 0100-530. The Type B protection function is particularly suitable for installations where electronic devices or frequency converters are used, as these often generate residual currents with direct current components or high frequencies. The short-time delayed tripping (10 ms) ensures selective disconnection, increasing the availability of the installation and avoiding unnecessary shutdowns.
Functions and Equipment in Detail
The breaker is equipped with a locking device that enables safe and controlled operation. It is designed for mounting on a DIN rail and occupies a width of 4 module units (TE). The mounting depth is 69 mm. The connection cross-sections for single-core and multi-core conductors are each up to 25 mm². The device dimensions are 70 mm (width), 85 mm (height), and 69 mm (depth). The color corresponds approximately to RAL number 7035. The frequency readiness is 50/60 Hz.
Technology Explained Simply
The circuit breaker detects residual currents flowing through the grounding and disconnects the power supply as soon as the preset value of 500 mA is exceeded. The short-time delayed tripping (10 ms) prevents the breaker from tripping during brief, non-hazardous disturbances, thereby increasing operational safety. The universal current sensitivity allows detection of residual currents consisting of direct or alternating current components, which is crucial for modern electronic installations. The impulse current withstand of 3 kA ensures that the breaker is not damaged even under high transient currents.
Compatibility and Accessories
Various accessories are available for this circuit breaker, extending its functionality. These include auxiliary switches such as the S2C-S/H6R (1 changeover contact for LS and FI) and the LS S2C-H6-11R. The Si-automat S200 B+ LS S2C-H6-20R is also available as a combinable device. These accessories enable integration into more complex circuits, for example for remote control or signal transmission.
Mounting and Installation
Mounting is done on a DIN rail, taking into account the mounting depth of 69 mm and the width of 4 TE. The terminals are designed for conductor cross-sections up to 25 mm², allowing both single-core and multi-core conductors to be used. The locking device facilitates safe handling during installation and maintenance.
Operational Advantages
The circuit breaker offers high system availability through short-time delayed tripping, avoiding unnecessary shutdowns. The universal current sensitivity ensures reliable protection in modern electronic installations. Compliance with standards DIN EN 62423 (Type B) and IEC/EN 61008-1, 61008-2-1, 61543 ensures conformity with applicable safety standards. Its use in households, commerce, and industry makes it a versatile protective device.
Residual current circuit breaker, Type B, universal current sensitive, short-time delayed, DIN rail, IP20