Further information for ABB Automation 2CSF204199R1630 residual current circuit breaker F204 A-63/0.03 110V
General
Number of poles
4
Rated current
63
Rated impulse withstand voltage Uimp
4
Mounting method
DIN rail
Leakage current type
A
Frequency
50/60 Hz
Degree of protection (IP)
IP20
Width in number of modular spacings
4
Built-in depth
69
Ambient temperature during operating
55
Pollution degree
2
Connectable conductor cross section multi-wired
25
Connectable conductor cross section solid-core
25
Depth of device
69
Height of device
85
RAL-number (akin)
7035
Width of device
70
Selective protection
Short-time delayed tripping
Additional equipment possible
With interlocking device
Explosion-proof
Residual current circuit breakers (RCCBs) offer personal and material protection as well as protection against electrically ignited fires in accordance with DIN VDE 0100-410 and DIN VDE 0100-530. The residual current circuit breakers of the F200 series guarantee protection against sinusoidal alternating currents and pulsating currents with a smooth DC residual current component of up to 6 mA against earth. As well as fault protection (protection against indirect contact), additional protection (with I¿n = 30 mA) and fire protection (with I¿n = 300 mA). Areas of application are mainly in commercial and industrial applications. The extensive range of accessories offers you everything you need for your installation tasks.
The F200 A 110 V series does not have VDE approval and is specifically designed for 110 V AC to 230/400 V AC applications. They meet the product standards IEC 61008-1, IEC 61008-2-1. The approvals are: CCC and UL 1053.