Further information for ABB 2CSF204101R1250 RCD 4-pole 25A
General
Number of poles
4
Rated current
25
Rated impulse withstand voltage Uimp
4
Mounting method
DIN rail
Leakage current type
A
Frequency
50/60 Hz
Degree of protection (IP)
IP20
Width in number of modular spacings
4
Built-in depth
69
Ambient temperature during operating
55
Pollution degree
2
Connectable conductor cross section multi-wired
25
Connectable conductor cross section solid-core
25
Depth of device
69
Height of device
85
Power loss
3.9
RAL-number (akin)
7035
Width of device
70
Selective protection
Short-time delayed tripping
Additional equipment possible
With interlocking device
Explosion-proof
The residual current circuit breaker F204 A-25/0.03 from ABB is a 4-pole protection switch for installation in electrical installations. It is designed for use in household, commercial, and industrial applications and provides protection against electrical hazards in accordance with DIN VDE 0100-410 and DIN VDE 0100-530. The switch ensures fault protection in case of indirect contact, additional protection with a rated residual current of 30 mA, and fire protection with a rated residual current of 300 mA. It is designed for sinusoidal alternating currents and pulsating currents with a smooth direct residual current component up to 6 mA. The protection functions are secured by compliance with product standards IEC/EN 61008-1, 61008-2-1, and 61543 (corresponding to VDE 0664-10, -11, -30) as well as UL 1053 for F200 A up to 100 A.
Residual current circuit breaker (RCCB) of the F200 series from ABB are designed for use in electrical installations requiring a high protection standard. The switch is rated for a nominal current of 25 A and features a rated impulse voltage withstand of 4 kV. The frequency operating safety is 50/60 Hz. The protection class IP20 ensures protection against contact with fingers and against solid foreign objects, but not against water or dust. The switch is designed for an ambient temperature up to 55 °C during operation. Pollution degree class 2 accounts for normal pollution that does not present special hazards. The mounting depth is 69 mm, and the device dimensions are 70 mm (width) × 85 mm (height) × 69 mm (depth). The width corresponds to 4 module units, enabling mounting on a DIN rail.
Residual current type A means that the switch can also detect and interrupt pulsating direct residual currents, which is important for installations with electronic devices. The switch is non-selective and not time-delayed, meaning it trips immediately upon detection of a residual current. The power loss is 3.9 W. The connection cross-sections for single-core and multi-core conductors are each 25 mm². The color corresponds to RAL number 7035, a gray tone commonly used in electrical installations.
Additional features can be attached to the switch, increasing flexibility during installation. An interlock device is integrated to prevent accidental operation. Mounting is done on a DIN rail, enabling standardized installation in enclosures.
Compatibility and accessories include various compatible components that extend functionality. These include the 4-pole busbar PS4/12 10 mm² for S200 F204 L1 L2 L3 N, the phase busbar PS3/9-FI for 1x F204+S200 L1 L2 L3 N L1 L2 L3 L1, the auxiliary switch LS S2C-H6-11R, the 3-phase busbar PS3/12FI for 1x F204+S200 L1 L2 L3 N removable, the Si-automat S200 B+ LS S2C-H6-20R, and the auxiliary switch S2C-S/H6R 1 changeover for LS and FI. These accessories allow application-specific adaptation of the switching system.
Mounting and installation are performed on a DIN rail, taking into account the mounting depth of 69 mm and the width of 4 module units. The interlock device supports safe handling. Compliance with the specified ambient temperature and pollution degree is important for reliable operation. The connection cross-sections of 25 mm² for single-core and multi-core conductors allow connection to corresponding cables.
Operational advantages lie in the reliability of the protection functions, compatibility with a wide range of accessories, and compliance with international standards. The integrated interlock device increases safety during operation. Compliance with standards IEC/EN 61008-1, 61008-2-1, and 61543 as well as UL 1053 ensures worldwide usability. Protection class IP20 and pollution degree 2 are suitable for indoor environments where no special environmental conditions exist.