Further information for ABB 2CSF202568R1160 RCD Type B 2P 16A
General
Number of poles
2
Rated current
16
Rated impulse withstand voltage Uimp
4
Mounting method
DIN rail
Leakage current type
B
Surge current capacity
3
Frequency
50/60 Hz
Degree of protection (IP)
IP20
Width in number of modular spacings
2
Built-in depth
69
Ambient temperature during operating
70
Pollution degree
3
Connectable conductor cross section solid-core
25
Depth of device
69
Height of device
85
Power loss
0.82
RAL-number (akin)
7035
Width of device
35
Selective protection
Short-time delayed tripping
Additional equipment possible
With interlocking device
Explosion-proof
The residual current circuit breaker F202 B-16/0.03 from ABB is a two-pole (2P) circuit breaker for mounting on DIN rail in electrical installations. It is specifically designed for use in systems with non-linear loads that generate smooth direct fault currents as well as pulsating or high-frequency fault currents, such as those occurring in frequency converters or electronic equipment. The breaker provides protection against indirect contact (fault protection), additional protection (at IΔn = 30 mA), and fire protection (at IΔn = 300 mA) in accordance with DIN VDE 0100-410 and DIN VDE 0100-530. It is universal current sensitive and detects fault currents in the frequency range of 0 to 2 kHz, making it suitable for modern electronic installations.
Applications
This circuit breaker is intended for use in residential, commercial, and industrial applications. It is particularly suitable for systems where electronic devices with non-linear current consumption are operated, as these often generate fault currents with direct current components or high frequencies that cannot be detected by conventional Type A breakers. The F200 B series ensures high system availability through the reliable detection of such fault currents.
Functions and Features in Detail
The breaker is of Type B, meaning it detects both sinusoidal alternating currents and pulsating currents as well as smooth direct fault currents. It features a short-time delayed tripping mechanism with a delay time of 10 ms, which supports selectivity in complex circuits. The rated current is 16 A, and the breaker is surge-current resistant up to 3 kA. The rated impulse voltage withstand is 4 kV. The protection class IP20 protects against contact with fingers and against solid foreign objects, but not against water or dust. The operating ambient temperature must not exceed 70 °C.
Technology Explained Simply
The breaker operates on the principle of residual current protection (RCCB). It monitors the current flow in the conductors and trips when an imbalance between incoming and outgoing current is detected, indicating a fault current. The universal current-sensitive design enables detection of direct fault currents that may occur in electronic devices. The frequency bandwidth of 0 to 2 kHz ensures that even high-frequency fault currents are detected. The power loss is 0.82 W, which is relevant for heat generation during operation.
Compatibility and Accessories
The breaker can be equipped with additional components, such as auxiliary switches. Compatible accessories include the S2C-S/H6R auxiliary switch 1 changeover for LS and FI, and the LS S2C-H6-11R auxiliary switch. These components enable integration into more complex control and switching systems. Mounting is on DIN rail, and the device dimensions are 35 mm (width), 85 mm (height), and 69 mm (depth). The mounting depth is 69 mm, and the width corresponds to 2 module units (2TE).
Mounting and Installation
Mounting is on a DIN rail, enabling standardized and secure installation in distribution boards. The mounting dimensions are designed for use in standard distribution boxes. The connection cross-sections for single-core conductors are up to 25 mm². The pollution degree classification 3 indicates that the breaker is suitable for environments with heavy contamination, such as those found in industrial installations.
Operational Advantages
The circuit breaker offers high reliability in systems with electronic loads, as it detects fault currents with direct current components and high frequencies. The short-time delayed tripping of 10 ms supports selectivity in complex circuits. The surge-current resistant design up to 3 kA ensures safety during short-circuit events. Compliance with standards DIN EN 62423 (Type B) and IEC/EN 61008-1, 61008-2-1, 61543 (Type A) ensures conformity with applicable safety requirements. The color corresponds to RAL 7035, providing a gray, metallic appearance common in technical installations.