Further information for ABB Automation 2CSB202325R1400 DDA202 F-40/0.03 FI block
General
Nominal voltage
230
Nominal current
40
Number of poles
2
Leakage current type
A
Surge current capacity
3
Rated insulation voltage Ui
500
Rated impulse withstand voltage Uimp
4
Connectable conductor cross section multi-wired
25
Degree of protection (IP)
IP2X
Pollution degree
2
Ambient temperature during operating
50
Power loss
3.2
Rated fault current adjustable
Delay adjustable
Anti-nuisance tripping version
With interlocking device
DDA200 Type F (mixed frequency sensitive)
The FI block (RCU) is for customer-side installation with automatic circuit breakers from the S200, S300 series. The resulting FI/LS combinations (RCBOs) offer personal and material protection as well as protection against electrically ignited fires in accordance with DIN VDE 0100-410 and DIN VDE 0100-530. They guarantee protection of 1P+N or 2P circuits against overload and short-circuit currents, protection against sinusoidal alternating currents and pulsating currents with a smooth DC residual current component of up to 10 mA against earth. As well as fault protection (protection against indirect contact), additional protection and fire protection. They meet the product standards IEC/EN 61009-1 (VDE 0664-20) Appendix G, IEC/EN 61009-2-1, DIN EN 62423 (VDE 0664-40).
Areas of application are household, commercial and industrial applications. The extensive range of accessories offers you everything you need for your installation tasks.
Optimal compromise between safety and operational continuity thanks to the interference immunity with surge current resistance (surge current form 8/20 µs) = 3,000 A against unwanted triggering and 10 ms short-term delay. The DDA202 F are mixed frequency sensitive especially for single-phase electronic consumers with frequency converters, with a frequency range of 1 - 1,000 Hz for detecting the fault current.