Further information for ABB Automation 2CSB202101R3400 FI block DDA202 A-40/0.3
General
Nominal voltage
400
Nominal current
40
Number of poles
2
Leakage current type
A
Rated insulation voltage Ui
500
Rated impulse withstand voltage Uimp
4
Connectable conductor cross section multi-wired
25
Degree of protection (IP)
IP2X
Pollution degree
2
Ambient temperature during operating
50
Power loss
3.2
Rated fault current adjustable
Delay adjustable
Anti-nuisance tripping version
With interlocking device
The residual current circuit breaker DDA202 A-40/0.3 from ABB is an RCD block (RCU) for customer-side mounting with circuit breakers from the S200 and S300 series. It serves as a basis for RCD/overcurrent combinations (RCBOs), ensuring personal and property protection as well as fire protection in accordance with DIN VDE 0100-410 and DIN VDE 0100-530. These combinations protect circuits with 1P+N, 2P, 3P, 3P+N or 4P against overload, short-circuit currents, and fault currents resulting from sinusoidal alternating currents and pulsating currents with a smooth direct current fault component up to 6 mA. The protection includes fault protection against indirect contact, additional protection with a rated residual current of 30 mA, and fire protection with 300 mA. The devices comply with product standard IEC/EN 61009 Annex G and are intended for use in household, commercial, and industrial applications.
Applications
The RCD block is designed for use in electrical installations where a combination of residual current and overcurrent protection is required. It is mounted in conjunction with circuit breakers from the S200 and S300 series to form RCBOs (Residual Current Breaker with Overcurrent). These are particularly common in residential buildings, commercial enterprises, and industrial facilities where reliable protection against electrical hazards and fires is necessary. The application takes place in switchboards, where the devices are installed in row-mounted form.
Functions and Equipment in Detail
The switch features a pole count of 2 and is designed for a rated voltage of 400 V. The rated current is 40 A, with the rated residual current being non-adjustable and fixed at 300 mA. The delay time is also non-adjustable, indicating immediate tripping upon reaching the residual current. The residual current type A enables protection against sinusoidal alternating currents and pulsating currents with a direct current component up to 6 mA. The rated insulation voltage Ui is 500 V, and the rated impulse withstand voltage Uimp is 4 kV, ensuring electrical strength under transient voltages. The protection class IP2X provides protection against finger contact and solid foreign objects, but not against water or dust. The ambient temperature during operation is up to 50 °C, ensuring suitability for normal indoor environments and slightly elevated temperatures. The power loss is 3.2 W, describing the thermal load during operation.
Technology Explained Simply
The RCD block functions as a component that connects with a circuit breaker to create an integrated protection function. The combination of residual current and overcurrent protection enables compact and efficient switchboard planning. The residual current type A is particularly important as it also detects pulsating currents with a direct current component, which can occur with modern electronic devices. The non-adjustable delay time means the switch trips immediately upon reaching the residual current, which is crucial for protection against electrical hazards. The protection class IP2X is sufficient for indoor installations, as it does not protect against water ingress or dust, but ensures mechanical safety. The rated insulation voltage of 500 V and impulse withstand voltage of 4 kV ensure electrical stability under normal and transient operating conditions.
Compatibility and Accessories
The RCD block is specifically designed for mounting with circuit breakers from the S200 and S300 series. It is compatible with various phase bar and busbar modules, including the phase bar PS3/24H, the 3-phase busbar PS3/12-E463, the end cap PS-END0, the busbar PS1/38/16H, the phase bar PS1/4, the phase bar PS2/48H, the 1-phase busbar PS1/6, the phase bar PS4/58N, the PS4/58/16NNA, the 1-phase busbar PS1/60/16, the PS1/3 PRO M Compact, the AST25/15QS connection terminal, the 2-phase busbar PS2/12 PRO M COMPACT, the PS4/58NNA, the PS4/48NHA, the PS3/15, the PS-END3, and the PS3/12FI. These accessories enable flexible and modular installation in switchboards. The combination with the mentioned bars and terminals ensures safe and proper connection of conductor cross-sections up to 25 mm².
Mounting and Installation
Mounting takes place in switchboards using row-mounted installation. The RCD block is attached to the designated mounting points of the S200 or S300 circuit breakers. The connection is made via the corresponding phase bar and busbar modules, ensuring safe and reliable power distribution. The connection cross-sections can be up to 25 mm², with the use of appropriate connection terminals such as the AST25/15QS recommended. Installation must comply with applicable standards and regulations, particularly DIN VDE 0100-410 and DIN VDE 0100-530. Mounting is intended for skilled personnel familiar with electrical installation.
Operational Advantages
The RCD block offers a compact and reliable solution for protecting electrical installations. The combination of residual current and overcurrent protection in a single device reduces space requirements in the switchboard and simplifies planning. The residual current type A ensures comprehensive protection, even against modern electronic loads. The non-adjustable delay time ensures immediate response in hazardous situations. The protection class IP2X and pollution degree 2 make the device suitable for indoor installations. The rated insulation voltage of 500 V and impulse withstand voltage of 4 kV ensure electrical stability. The power loss of 3.2 W is low compared to other devices, minimizing thermal load. Compatibility with a wide range of accessories enables flexible and adaptable installation.
Rated Switching Capacity
The rated switching capacity is 6 kA when mounted with MCB S200, 10 kA with S200 M, and 25 kA with S300 P. This describes the maximum current the device can safely interrupt without damage. These values are crucial for selecting the correct combination of RCD block and circuit breaker to meet the requirements of the respective installation.
Connection Cross-Section
The connected conductor cross-section can be up to 25 mm², with the use of suitable connection terminals such as the AST25/15QS recommended to ensure a safe and reliable connection. The use of stranded conductors is permitted, provided the maximum cross-section of 25 mm² is not exceeded.
Accessories
Compatible accessories include various phase bar and busbar modules, end caps, and connection terminals, enabling flexible and modular installation in switchboards. The mentioned modules are specifically designed for use with the RCD block DDA202 A-40/0.3 and ensure safe and reliable power distribution.
Protection Class and Environment
The protection class IP2X protects against finger contact and solid foreign objects, but is not suitable for outdoor use or humid environments. The maximum ambient temperature during operation is 50 °C, ensuring suitability for normal indoor environments.
Compliance with Standards
The device complies with product standard IEC/EN 61009 Annex G and is certified for use in accordance with DIN VDE 0100-410 and DIN VDE 0100-530. These standards guarantee protection against electrical hazards and fires and are required for installation in residential and commercial buildings.
Rated Residual Current
The rated residual current is 300 mA, which is sufficient for fire protection. Additionally, the switch provides supplementary protection with 30 mA, relevant for personal and property protection. The non-adjustable delay time ensures immediate tripping upon reaching the residual current.
Combination with Circuit Breakers
The RCD block is designed for mounting with circuit breakers from the S200 and S300 series. The combination results in RCBOs, providing both residual current and overcurrent protection. Selecting the correct combination is essential for the safety and reliability of the electrical installation.
Application Areas
Application areas include household, commercial, and industrial applications where reliable protection against electrical hazards and fires is required. The devices are suitable for switchboards in residential buildings, office buildings, production facilities, and other facilities.