ABB 2CSA275901R9135, EAN: 8012542342014

ABB Automation 2CSA275901R9135 S-ARC1 M B13 fire protection switch

ABB Automation 2CSA275901R9135 S-ARC1 M B13 fire protection switch

Lieske Part No. 326285
Mfg Part No 2CSA275901R9135
EAN-Code 8012542342014
Manufacturer ABB
Here only 245,38 EUR
292,00 EUR incl. VAT

Further information for ABB Automation 2CSA275901R9135 S-ARC1 M B13 fire protection switch

General
Release characteristicB
Number of poles2
Rated current13
Rated voltage240
Rated short-circuit breaking capacity IEC 60947-210
Voltage typeAC
Current limiting class3
Over voltage category3
Pollution degree2
Width in number of modular spacings2
Built-in depth69
Additional equipment attached at deliveryFire protection switch
Frequency50
Concurrently switching N-neutralyes
The ABB S-ARC1 M B13 is an arc fault detection device (AFDD) with integrated circuit breaker (MCB), compliant with IEC/EN 62606 (VDE 0665-10) and IEC/EN 60898-1 (VDE 0641-11). The device provides protection for electrical installations against series and parallel arc faults, overcurrent (overload or short circuit), as well as internal overvoltage protection. It meets the requirements for protection against electrically initiated fires according to DIN VDE 0100-420. The device is 2-pole switching and 1-pole protected (LS), with the neutral conductor switching simultaneously. The tripping characteristic is B, the rated current is 13 A, and the rated voltage is 240 V AC at a frequency of 50 Hz. The rated breaking capacity according to IEC 60947-2 is 10 kA, and the rated switching capacity according to IEC/EN 60898-1 is 6 kA. The energy limitation class is 3, the overvoltage category is 3, and the pollution degree is 2. The unit has a width of 2 module units and an installation depth of 69 mm. A fire protection switch is integrated as standard.

Applications

The S-ARC1 M B13 is mandatory in single-phase AC systems with a rated current of 16 A, particularly in sleeping or living rooms of homes, day care facilities for children, disabled or elderly people, and barrier-free apartments. It is also required in rooms or locations with special fire risk, fire-hazardous workplaces, buildings predominantly made of combustible materials (e.g. wooden houses), as well as in final circuits supplying or passing through electrical equipment in the mentioned areas. Its use is recommended in rooms with sleeping facilities, fire-spreading structures, or final circuits with high connected load. Generally, the device serves to enhance fire protection against electrically initiated fires.

Functions and Equipment in Detail

The device features an LED indicator that allows identification of the cause of tripping. Power supply can be from top or bottom, enabling flexible mounting in switchboards. Cross-wiring, for example to residual current devices, is possible in the rear terminal area. The device is part of the System pro M compact® and allows mounting of accessory components such as auxiliary switches. The integrated arc fault detection recognizes both series and parallel arcs, which are often not detected before and can lead to fires.

Technology Explained Simply

The combination of AFDD and MCB provides multiple protection: The MCB protects against overload and short circuit, while the AFDD specifically responds to arc faults, which often arise from damaged insulation or loose connections. Energy limitation class 3 means that the device limits energy development during a fault to minimize damage. Overvoltage category 3 indicates that the device is suitable for installations with moderate overvoltage stress. Pollution degree 2 means the device is designed for environments with low pollution, such as indoor spaces.

Compatibility and Accessories

The device is compatible with accessories from the System pro M compact®. Suitable accessories include auxiliary switches such as the LS S2C-H6-11R, the S2C-S/H6R (1 changeover contact for LS and RCD), and the Si-automat S200 B+ LS S2C-H6-20R. These components can be connected to extend functions, such as signal input and output.

Mounting and Installation

Mounting is carried out in standard switchboards. The unit is designed for an installation depth of 69 mm and has a width of 2 module units. Power supply can be from top or bottom, allowing flexible positioning. Cross-wiring in the rear terminal area facilitates integration into existing switchgear. Installation is carried out in accordance with applicable regulations and standards, particularly DIN VDE 0100-420.

Operational Advantages

The S-ARC1 M B13 provides comprehensive protection against electrically initiated fires, thereby improving safety in sensitive areas such as care facilities or apartments with increased fire risk. The combination of arc fault detection and MCB protection reduces the risk of unintended power outages and damage. The LED indicator enables quick diagnosis of the tripping cause, accelerating maintenance and fault repair. Integration into the System pro M compact® ensures modular expandability and compatibility with other components.