Further information for ABB Automation 2CDS273103R0134 S203M-C13NA circuit breaker 3P+NA
General
Release characteristic
C
Number of poles (total)
4
Number of protected poles
3
Rated current
13
Rated voltage
400
Rated insulation voltage Ui
440
Rated impulse withstand voltage Uimp
4
Rated short-circuit breaking capacity Icn EN 60898 at 230 V
10
Voltage type
AC
Frequency
60
Current limiting class
3
Over voltage category
3
Pollution degree
3
Width in number of modular spacings
4
Built-in depth
69
Degree of protection (IP)
IP20
Ambient temperature during operating
55
Connectable conductor cross section multi-wired
25
Connectable conductor cross section solid-core
35
Power loss
9.2
Concurrently switching N-neutral
Additional equipment possible
Explosion-proof
Flush-mounted installation
The circuit breakers of the S 200 M series protect cables and lines against overload and short circuit in accordance with DIN VDE 0100-430 and DIN VDE 0100-530. They comply with the construction regulations DIN VDE 0641-11 or IEC/EN 60898-1, DIN VDE 0660-101 or IEC/EN60947-2 and UL1077 and CSA 22.2 No. 235. Their patented connection terminal ensures simple and safe contacting and handling using a pressure plate. For better visibility when wiring, the connection opening for cables is located above the connection opening for the phase busbar. Conductor cross-sections of up to 35 mm² can be connected directly to the device via the connection terminal with insulation in protection class IP20. The extensive range of accessories offers you everything you need for your installation tasks. Numerous approvals make the S 200 M fit for worldwide use. Each device undergoes three intensive tests for quality and performance before delivery.