Further information for ABB Automation SU202MR-K2 circuit breaker 2P 2 A
General
Release characteristic
K
Number of poles (total)
2
Number of protected poles
2
Rated current
2
Rated voltage
400
Rated insulation voltage Ui
400
Rated impulse withstand voltage Uimp
4
Rated short-circuit breaking capacity Icn EN 60898 at 230 V
10
Voltage type
AC
Frequency
60
Current limiting class
3
Over voltage category
3
Pollution degree
3
Width in number of modular spacings
2
Built-in depth
69
Degree of protection (IP)
IP20
Ambient temperature during operating
55
Connectable conductor cross section multi-wired
25
Connectable conductor cross section solid-core
35
Power loss
3.6
Concurrently switching N-neutral
Additional equipment possible
Explosion-proof
Flush-mounted installation
The circuit breakers of the SU 200 MR series protect cables and lines against overload and short circuit in accordance with DIN VDE 0100-430 and DIN VDE 0100-530. They comply with the construction regulations DIN VDE 0660-101 or IEC/EN60947-2 and UL489 or CSA 22.2 No. 5. The captive screw of the connection opening for M5 ring cable lugs ensures a constant connection. The extensive range of accessories offers you everything you need for your installation tasks. Each device is subjected to intensive quality and performance tests three times before delivery.