Further information for ABB Automation 2CDS253001R0805 S203-B80 circuit breaker 80A 3P
General
Release characteristic
B
Number of poles (total)
3
Number of protected poles
3
Rated current
80
Rated voltage
400
Rated insulation voltage Ui
440
Rated impulse withstand voltage Uimp
4
Rated short-circuit breaking capacity Icn EN 60898 at 230 V
6
Rated short-circuit breaking capacity Icn EN 60898 at 400 V
6
Voltage type
AC
Frequency
60
Current limiting class
3
Over voltage category
3
Pollution degree
3
Width in number of modular spacings
3
Built-in depth
69
Degree of protection (IP)
IP20
Ambient temperature during operating
55
Connectable conductor cross section multi-wired
35
Connectable conductor cross section solid-core
50
Power loss
24.3
Concurrently switching N-neutral
Additional equipment possible
Explosion-proof
Flush-mounted installation
The S203-B80 circuit breaker from ABB is a circuit protection switch for use in electrical installations. It protects cables and wiring against overload and short circuit in accordance with DIN VDE 0100-430 and DIN VDE 0100-530. The device complies with construction regulations DIN VDE 0641-11 or IEC/EN 60898-1, as well as DIN VDE 0660-101 or IEC/EN 60947-2. With a rated current of 80 A and a rated voltage of 400 V AC, it is designed for use in three-phase AC systems. The B tripping characteristic ensures precise response to overloads and short circuits. The switch features a rated insulation voltage Ui of 440 V and a rated impulse voltage withstand Uimp of 4 kV, making it suitable for applications in overvoltage category 3. Energy limitation class 3 and pollution degree 3 highlight its reliability under industrial conditions.
Applications
The S203-B80 is intended for use in electrical distributions indoors. It is not designed for flush mounting and meets the protection rating IP20, meaning it is protected against contact with fingers and against solid foreign objects, but not against splashing water or dust. The ambient temperature during operation is up to 55 °C. The application is in networks with a frequency of 60 Hz.
Functions and Equipment in Detail
The device features a patented connection terminal that enables simple and secure connection. Operation is performed via a pressure plate, ensuring a secure connection. The cable connection opening is located above the connection opening for the phase bar, providing better visibility during wiring. Direct connection to the terminal is possible for conductor cross-sections up to 50 mm² single-core and up to 35 mm² multi-core. The terminal is insulated and meets protection class IP20. The mounting depth is 69 mm, and the device occupies a width of 3 module units.
Technology Explained Simply
The circuit breaker automatically disconnects in case of overloads and short circuits to protect connected wiring and devices. The B tripping characteristic means the switch trips within seconds at a current of approximately 3 to 5 times the rated current. In the event of a short-circuit current of 6 kA (rated switching capacity Icn), it disconnects within milliseconds. The rated voltage of 400 V AC and the rated insulation voltage of 440 V ensure electrical safety in standard networks. The rated impulse voltage withstand of 4 kV protects the device against transient voltage surges.
Compatibility and Accessories
Various accessories are available for the S203-B80 to support installation and operation. These include the series terminals CMS-102PS and CMS-101PS, suitable for secure connection of cables in series distributions. These accessories enable structured and reliable wiring in enclosures and distributions.
Mounting and Installation
Mounting is performed in series distributions, where the device occupies a width of 3 module units. The mounting depth of 69 mm must be considered when planning the enclosure depth. The connection terminal allows direct connection of cables without additional tools. Wiring is done via the upper cable connection opening, ensuring clear visibility of the wiring.
Operational Advantages
The S203-B80 offers high reliability due to its design features such as the patented connection terminal and the precise B tripping characteristic. The direct connection capability for conductor cross-sections up to 50 mm² single-core and 35 mm² multi-core reduces the number of required transition terminals. The IP20 protection rating and compliance with standards IEC/EN 60898-1 and IEC/EN 60947-2 ensure safety and proper operation in electrical installations. The power loss is 24.3 W, which should be considered when planning heat dissipation in enclosures.
Each device undergoes three intensive quality and performance tests before delivery to ensure functional reliability. Compatibility with the mentioned series terminals enables flexible and secure integration into existing distributions.