Further information for ABB 2CDS251001R0205 Circuit Breaker 20A 1-pole B
General
Release characteristic
B
Number of poles (total)
1
Number of protected poles
1
Rated current
20
Rated voltage
230
Rated insulation voltage Ui
440
Rated impulse withstand voltage Uimp
4
Rated short-circuit breaking capacity Icn EN 60898 at 230 V
6
Rated short-circuit breaking capacity Icn EN 60898 at 400 V
6
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V
10
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V
10
Voltage type
AC/DC
Frequency
60
Current limiting class
3
Over voltage category
3
Pollution degree
3
Width in number of modular spacings
1
Built-in depth
69
Degree of protection (IP)
IP20
Ambient temperature during operating
55
Connectable conductor cross section multi-wired
25
Connectable conductor cross section solid-core
35
Power loss
2.5
Concurrently switching N-neutral
Additional equipment possible
Explosion-proof
Flush-mounted installation
The S201-B20 circuit breaker from ABB is a 1-pole fuse switch of the S 200 series, designed for use in electrical installations to protect cables and lines against overload and short circuit. It complies with standards DIN VDE 0100-430 and DIN VDE 0100-530, as well as construction regulations DIN VDE 0641-11, IEC/EN 60898-1, DIN VDE 0660-101 and IEC/EN 60947-2. Additionally, it is certified according to UL1077, highlighting its suitability for worldwide use. The device is rated for a nominal voltage of 230 V and a nominal insulation voltage Ui of 440 V, with a nominal impulse voltage withstand Uimp of 4 kV. The rated current is 20 A, and the tripping characteristic is B, representing a typical curve for protecting lines in residential and small commercial installations.
Applications
The S201-B20 is intended for use in indoor installations, particularly in enclosures and distributions, where safe and reliable protection of electrical lines is required. It is not designed for flush mounting and meets protection class IP20, meaning it is protected against contact with fingers and against solid foreign objects, but not against splashing water or dust. The ambient temperature during operation must not exceed 55 °C.
Functions and Equipment in Detail
The device features a patented connection terminal that enables simple and secure connection. The connection is made via a pressure plate, ensuring a reliable and mechanically stable connection. The cable connection opening is positioned above the phase bar connection opening, providing better visibility during wiring. Direct connections to the terminal can be made with conductor cross-sections up to 35 mm² (single-strand) and 25 mm² (multi-strand). The connection terminal is insulated and meets protection class IP20.
Technology Explained Simply
The circuit breaker is designed for AC/DC voltage type and can be operated at a frequency of 60 Hz. The energy limitation class is 3, indicating limited energy release during a short circuit. The rated switching capacity Icn is 6 kA at 230 V and 6 kA at 400 V according to EN 60898. The rated switching capacity Icu according to IEC 60947-2 is 10 kA at 230 V and 10 kA at 400 V. These values define the maximum current the switch can safely interrupt without damage. The overvoltage category is 3, and the pollution degree is 3, indicating suitability for use in environments with increased pollution risk. The mounting depth is 69 mm, and the width corresponds to one module width.
Compatibility and Accessories
The S201-B20 is designed for use in the Compact system and can be combined with various accessories. These include busbars such as PS3/6, PS3/9 and PS3/12 with end cap, as well as row terminals CMS-101PS and CMS-102PS. Additionally, a three-phase set 710SPM with 10 mm² cross-section and a length of 1056 mm is available, as well as a 3-phase busbar for cutting with 10 mm² cross-section and 60 modules. These components enable flexible and modular installation in enclosures.
Mounting and Installation
Mounting is carried out in enclosures or distributions within the Compact system. The mounting height is 69 mm, and the device occupies one module width. The connection terminal allows direct connection of cables with the specified cross-sections. The phase bar connection opening is located below the conductor connection opening, facilitating wiring. The power loss is 2.5 W, which should be considered in the thermal management planning of the control panel.
Advantages in Operation
The S201-B20 provides reliable protection through the B characteristic, suitable for typical loads in residential and small commercial installations. The patented connection terminal ensures secure and easy installation. Certifications according to international standards enable use in various markets. The modular design within the Compact system allows flexible expansion and combination with other components. Each device undergoes three intensive tests before delivery to ensure quality and performance.