Further information for ABB Automation 2CDL240114R1648 PS4/48/16NHA phase bar 4-phase
General
Number of phases
4
Number of poles
48
Suitable for number of devices
12
Pitch dimensions
17.5
Cross section
16
Length
1047
Rated permanent current Iu
80
Type of electric connection
Pin
Max. rated operation voltage Ue
690
Rated short-time withstand current lcw
25
Colour
Grey
Width in number of modular spacings
60
Insulated
Suitable for devices with N-busbar
Suitable for devices with auxiliary switch
The ABB phase bar type PS4/48/16NHA is a modular, 4-phase bar for safe and economical cross-wiring of circuit breakers, residual current protective devices and other modular installation devices in meter enclosures and distributors. With a pole count of 48 and a connection cross-section of 16 mm², it is designed for a rated continuous current of 80 A. The bar features a pin connection and is insulated, ensuring safe electrical isolation. The maximum rated operating voltage is 690 V, and the rated short-time withstand current is 25 kA, making the bar suitable for use in industrial and commercial installations. The width is 60 module units, with a module pitch of 17.5 mm, and the total length of the bar is 1047 mm. The colour is grey, enabling good visibility and integration into standard distributor enclosures.
Applications
The phase bar is designed for use in meter enclosures and distributors, particularly in installations where multiple modular devices are connected in parallel. It is suitable for devices with a neutral conductor and for devices with auxiliary switches, making it flexible for various switching configurations. The bar can supply up to 12 devices, with the number of modules varying depending on device type and connection method. The 4-phase configuration enables supply of 3-phase loads as well as the neutral conductor, which is common in industrial electrical installations.
Functions and Equipment in Detail
The bar is equipped with a pin connection, ensuring a secure and mechanically stable connection to the devices. The insulation of the bar protects against unintended contact and prevents short circuits. The rated short-time withstand current of 25 kA protects the bar against thermal and mechanical stress during short-circuit events. The maximum operating voltage of 690 V makes the bar suitable for high-voltage installations, which are common in industry and commerce. The pole count of 48 allows connection of up to 12 devices, with the exact number depending on the specific device configuration.
Technology Explained Simply
The phase bar serves as a central power distribution unit, supplying multiple electrical devices via a common circuit. The cross-section of 16 mm² ensures sufficient current-carrying capacity for the rated continuous current of 80 A. The insulation protects against electrical hazards and ensures safe installation. The 4-phase configuration enables supply of 3-phase loads as well as the neutral conductor, which is common in industrial electrical installations. The rated short-time withstand current of 25 kA protects the bar against thermal and mechanical stress during short-circuit events.
Compatibility and Accessories
The phase bar is compatible with circuit breakers, residual current protective devices and other modular installation devices. It is suitable for devices with a neutral conductor and auxiliary switches, enabling flexible application in various switching configurations. Suitable accessories include the BSK shock protection, which provides additional protection against unintended contact and increases safety during installation and maintenance.
Mounting and Installation
Installation takes place in meter enclosures and distributors, where the bar is inserted into the designated modules. The pin connections enable a secure and mechanically stable connection to the devices. The insulation of the bar protects against unintended contact and prevents short circuits. Installation is carried out according to the specifications of the respective device manufacturers and applicable standards for electrical installations.
Operational Advantages
The phase bar enables economical and safe cross-wiring of multiple devices, reducing installation time and simplifying maintenance. The insulation and high short-time withstand current increase the safety and reliability of the installation. Compatibility with various device types and support for auxiliary switches and neutral conductors expand application possibilities. The grey colour and standardised width of 60 module units enable easy integration into existing distributor enclosures.