Further information for ABB Automation 2CDL210010R1060 PS1/60A phase bar
General
Number of phases
1
Number of poles
60
Suitable for number of devices
60
Pitch dimensions
17.5
Cross section
10
Length
1050
Rated permanent current Iu
63
Type of electric connection
Pin
Max. rated operation voltage Ue
690
Rated short-time withstand current lcw
25
Colour
Grey
Width in number of modular spacings
60
Insulated
Suitable for devices with N-busbar
Suitable for devices with auxiliary switch
The ABB phase bar type PS1/60A is a modular component for busbar distribution systems, enabling safe and cost-effective cross-wiring of circuit breakers, residual current protective devices, and other modular installation devices. It is designed for use in single-phase systems and features a pole count of 60, corresponding to a width of 60 module units. The bar is equipped with a connection cross-section of 10 mm² and is suitable for a maximum rated operating voltage of 690 V. The rated continuous current is 63 A, with the bar exhibiting a rated short-time withstand current of 25 kA. The electrical connection is made via pin terminals, ensuring a secure connection. The bar is insulated and finished in grey, allowing for seamless integration into standard distribution boxes. The length is 1050 mm, with a module pitch of 17.5 mm. The bar is not designed for devices with a neutral conductor or auxiliary switches.
Applications
The phase bar PS1/60A is used in electrical distribution boards to electrically connect multiple devices within a single phase. It is particularly suitable for installations requiring parallel operation of multiple circuit breakers or residual current protective devices. The bar enables a structured and clear installation, facilitating maintenance and servicing. Due to its insulation and defined current-carrying capacity, it is suitable for use in industrial and commercial electrical installations.
Functions and Features in Detail
The bar is designed for connecting up to 60 devices, with the number of modules directly corresponding to the width in module units. The pin terminals ensure a mechanically stable and electrically reliable connection. The insulation protects against unintended contact and short circuits. The grey finish is standard in distribution boards and enhances visual clarity. The bar is not designed for devices with a neutral conductor or auxiliary switches, which must be considered during installation planning.
Technology Explained Simply
The rated continuous current of 63 A means the bar can be continuously loaded with up to 63 amperes without overheating or damage. The rated short-time withstand current of 25 kA indicates the maximum current the bar can withstand for a short duration (typically 1 second) without damage—an important safety parameter during short-circuit events. The connection cross-section of 10 mm² corresponds to a standard value for medium to high loads in distribution boards. The insulation protects against electrical hazards and enables safe installation in enclosed distribution boards.
Compatibility and Accessories
The phase bar is compatible with circuit breakers, residual current protective devices, and other modular installation devices designed for use with pin terminals. Suitable accessories include the BSK shock protection, which enhances safety during installation and maintenance by preventing unintended contact with live parts. The bar is not intended for devices with a neutral conductor or auxiliary switches, which must be considered when selecting devices.
Mounting and Installation
Mounting is performed in a distribution box, where the bar is inserted into the designated busbar holders. Devices are connected to the bar via pin terminals. The insulation and fixed pole count facilitate correct positioning and connection of devices. The length of 1050 mm and module pitch of 17.5 mm allow precise adaptation to the specific distribution configuration. Mounting does not require special tools, but correct alignment and connection of devices must be ensured.
Operational Advantages
Using the PS1/60A provides a clear and structured distribution of electrical wiring, simplifying maintenance and fault diagnosis. The insulation increases operational safety, and the high current-carrying capacity ensures reliability under load. Standardization of dimensions and connection cross-section enables easy integration into existing systems. The bar is optimized for single-phase systems and offers an economical solution for cross-wiring multiple devices.