Further information for ABB Automation 2CDL010101R1639 PS 1/39/16 ILTS-E phase bar 1-Ph 9 pins 16 mm²
General
Number of phases
1
Number of poles
39
Suitable for number of devices
39
Pitch dimensions
17.5
Cross section
16
Length
1050
Rated permanent current Iu
80
Type of electric connection
Pin
Max. rated operation voltage Ue
690
Rated short-time withstand current lcw
25
Colour
Grey
Width in number of modular spacings
60
Insulated
Suitable for devices with N-busbar
Suitable for devices with auxiliary switch
ABB Phase busbar distributor PS 1/39/16 ILTS-E is designed for safe and economical cross-wiring of modular installation devices such as circuit breakers and residual current protective devices. The system enables structured and efficient power distribution in enclosures and distribution boxes. The busbar is designed for single-phase supply and features 39 modules, making it suitable for up to 39 devices. The unit is supplied in grey, with a cross-section of 16 mm² and a pitch of 17.5 mm. The length is 1050 mm, and the width corresponds to 60 pitch units. Electrical connections are made via pin connectors, which are insulated to ensure a safe connection.
Applications
Phase busbar distributors are used in industrial and commercial electrical installations, particularly in enclosures where modular and flexible power distribution is required. They are intended for use with devices that do not require a neutral conductor or auxiliary switches. The busbar is rated for a maximum operating voltage of 690 V and can carry a rated continuous current of 80 A. The rated short-time withstand current is 25 kA, making the busbar suitable for use in installations with high short-circuit loads.
Functions and Equipment in Detail
The busbar is specifically designed for use with ILTS-E modules, with the 39 modules enabling even distribution of electrical load. The pin connectors ensure a reliable electrical connection, further protected by insulation. The construction with a cross-section of 16 mm² ensures sufficient current-carrying capacity to meet requirements in medium to high load ranges. The busbar is not intended for devices with neutral conductors or auxiliary switches, which must be considered during installation planning.
Technology Explained Simply
Phase busbar distributors operate on the principle of parallel power distribution, where current is distributed along the entire length of the busbar. Insulation of the pin connectors prevents unintended contact and short circuits. The pitch of 17.5 mm corresponds to the standard for modular enclosure components, enabling compatible mounting with standard devices. The rated short-time withstand current of 25 kA indicates that the busbar can safely withstand short-term current surges in the event of a fault without damage.
Compatibility and Accessories
The busbar is specifically designed for ILTS-E modules and can be combined with circuit breakers and residual current protective devices that do not require neutral conductors or auxiliary switches. Use with other module types is not intended. The busbar is not suitable for devices with auxiliary switches mounted on the right or bottom, as these could interfere with mounting and electrical connection.
Mounting and Installation
Mounting is carried out in enclosures or distribution boxes, where the busbar is inserted into the designated mounting openings. Modules are attached to the pin connectors, with insulation ensuring electrical safety. The busbar is not cuttable, as it is supplied in the standard length of 1050 mm. Mounting requires no additional tools or components, as the busbar is directly installed into the designated modules.
single-phase power distribution, modular installation, pin connection, insulated connection, ILTS-E module, rated short-time withstand current
Operational Advantages
Phase busbar distributors provide clear and organized power distribution, simplifying maintenance and servicing. The modular structure allows flexible adaptation to different requirements, while insulation of the connections enhances safety. High current-carrying capacity and short-time withstand current ensure reliable operation even under demanding conditions. The busbar is suitable for use in industrial and commercial installations where safe and efficient power distribution is required.