| General |
| Number of poles | 2 |
| Rated voltage | 400 |
| Rated current | 63 |
The ABB switch disconnector type ILTS-E2D0, manufacturer's number 2CDE102001R1901, is an industrial fuse switch disconnector with plug-in technology, specifically designed for fuse inserts of standard D0 with rated currents from 2 to 63 A. It serves for the safe disconnection of electrical installations during operation and enables the replacement of fuse inserts only in the de-energized state, thus increasing work safety. The switch is designed for use in industrial and commercial electrical installations where reliable and user-friendly disconnection of power supply is required.
Applications
The ILTS-E2D0 is used in installations where phase- and current-independent disconnection of power supply is necessary, for example in machine controls, distribution systems, or during maintenance of electrical devices. The plug-in technology enables quick and safe mounting and dismounting of the switch in distributions. The use of D02 or D01 fuse inserts with reducing piece extends compatibility with various protection configurations.
Functions and equipment in detail
The switch features a latching mechanism that ensures the fuse insert cannot be accidentally removed while the switch is under voltage. The non-removable fuse insert holder ensures the insert does not get lost during operation. The two-part frame terminals mounted on both sides allow flexible wiring, with the lower terminal supporting cross-wiring, simplifying installation in distributions. An integrated auxiliary switch indicates the current switching position, facilitating inspection of the operating status.
Technology explained clearly
The switch disconnector ILTS-E2D0 is rated for a nominal voltage of 400 V and a nominal current of 63 A. These values define the maximum operating conditions under which the switch functions safely and reliably. The pole count is 2, meaning the switch can disconnect two electrical conductors (phases). The plug-in technology enables modular integration into distributions, where the switch is inserted into a phase rail. Disconnection is achieved mechanically via the switch lever, ensuring a secure power disconnection.
Compatibility and accessories
The switch is compatible with various phase rail and end cap models specifically developed for the ILTS-E series. Compatible accessories include, for example, the end cap PS-END (2CDL200001R0001), the end cap END1.1, the PS-END3 end cap for phase rail (2CDL200001R3001), as well as phase rail models such as PS 3/39/16 ILTS-E (3-phase, 16 mm²) or PS 1/39/30 ILTS-E (1-phase, 30 mm²). An auxiliary switch ILTS-E/H11 can be used additionally to realize additional signals or control functions.
Mounting and installation
Mounting is carried out in distributions equipped with an appropriate phase rail. The switch is inserted into the rail and mechanically fixed. The terminals are designed for secure connection with cables, with cross-wiring in the lower terminal simplifying cabling in distributions with multiple switches. Installation must be carried out in accordance with applicable regulations for electrical installations, ensuring power disconnection before mounting.
Advantages in operation
The ILTS-E2D0 offers high operational safety through the mechanical interlock of the fuse insert, which can only be opened in the de-energized state. The integrated indication of switching position enables quick visual inspection of the operating status. The plug-in technology and cross-wiring reduce installation time and increase flexibility in planning distributions. The use of standard D0 fuse inserts ensures broad compatibility with existing protection systems.