Further information for ABB 1SVR560730R3401 CM-UFD.M31 Grid Feed-in Monitoring
General
Type of electric connection
Screw connection
Voltage measurement range 1
540
Voltage measurement range 2
540
Type of voltage measurement range
AC
Response value voltage
540
Min. adjustable delay-on energization time
1
Min. adjustable off-delay time
1
Width
108
Height
90
Depth
67
Operating voltage at AC 50 Hz
230
Operating voltage at AC 60 Hz
230
Rated switch current
4
Supply voltage AC 50 Hz
240
Supply voltage AC 60 Hz
240
Supply voltage DC
240
Voltage type (operating voltage)
AC/DC
Voltage type of supply voltage
AC/DC
With detachable clamps
Single-phase under voltage possible
Three-phase under voltage possible
Single-phase over voltage possible
Three-phase over voltage possible
Single-phase hysteresis possible
Three-phase hysteresis possible
Contains function DC-under voltage
Contains function DC-over voltage
Contains function DC-voltage hysteresis
External power supply required
The CM-UFD.M31 grid feed-in monitoring relay monitors voltage and frequency in single-phase and three-phase networks. In conjunction with inverters with integrated island network detection, it meets the conditions for NA protection according to VDE-AR-N 4105:2018-11 (generation systems on the low-voltage network) or VDE-AR-N 4110:2018-11 (generation systems on the medium-voltage network). For use in old systems, the setting values according to VDE-AR-N 4105:2011 or BDEW (feed-in to the medium-voltage network) can also be selected. The last 99 shutdown causes and their respective times are stored in an alarm memory. The connected coupling switches are also monitored, vector shift detection and ROCOF frequency gradient monitoring are carried out.