Further information for ABB Automation 1SFL647001R7022 contactor AF1250-30-22-70
General
Rated control supply voltage Us at AC 50HZ
250
Rated control supply voltage Us at AC 60HZ
250
Rated control supply voltage Us at DC
250
Voltage type for actuating
AC/DC
Rated operation current Ie at AC-1, 400 V
1260
Number of auxiliary contacts as normally open contact
2
Number of auxiliary contacts as normally closed contact
2
Type of electrical connection of main circuit
Screw connection
Number of normally closed contacts as main contact
0
Number of main contacts as normally open contact
3
Depth
242
Height
344
Operating voltage at AC 50 Hz
1000
Operating voltage at AC 60 Hz
1000
Width
210
Modular version
Contactors AF1250 to AF2650 from 1260 to 2650 A AC-1 (400 V) represent the compact series with AC/DC control and very wide coil voltage ranges. Only 4 coils cover control voltages from 20...500 VDC to 24...500 VAC - without additional suppression elements required. The contactors also have a 24 VDC input and can therefore be controlled directly from a PLC. This means they can be used worldwide and with only a small variation. These contactors are mostly used in AC-1 power circuits in wind and solar technology. Attachable accessories include up to 2 2-pole auxiliary switches that can be mounted on the right and left sides. The auxiliary break contacts of two auxiliary switches mounted on the right and left, connected in series, act as mirror contacts in accordance with IEC60947-5-1 Appendix L. Additional accessories such as terminal covers, wiring aids and locking elements, etc., complete the range.