Further information for ABB 1SEP620020R3000 Safety Disconnect Switch 3-pole
General
Max. rated operation voltage Ue AC
1000
Rated permanent current Iu
160
Conditioned rated short-circuit current Iq
120
Suitable for fuses
NH00
Number of poles
3
Type of electrical connection of main circuit
Bolt connection
Cable entry
Below
Type of control element
Other
Position control element
Front side
Degree of protection (IP), front side
IP30
Version as main switch
Version as safety switch
With error protection
Equipped with connectors
Suitable for busbar mounting
Motor drive optional
Motor drive integrated
Version as emergency stop installation
Floor mounting
Front mounting
The ABB switch disconnector type ZHBM00-3P-M8 is a 3-pole switch designed for use in power distribution networks, specifically designed for mounting on phase busbars with a spacing of 185 mm. It belongs to the InLine II device generation and is designed for use with NH fuse inserts of size 00. The series is tested in accordance with EN / IEC 60947-3 and provides a stable and secure solution for the operation and maintenance of switchgear. The switch is designed for a maximum rated operating voltage of 1000 V AC and features a rated continuous current of 160 A. The conditional rated short-circuit current is 120 kA, making it suitable for applications with high short-circuit loads. The degree of protection on the front side is IP30, providing protection against solid foreign objects and splashing water from the front.
Applications
The switch disconnector ZHBM00-3P-M8 is intended for use in industrial and commercial electrical installations, particularly in switchgear where secure disconnection of the circuit is required. It is commonly used in distribution switches, main distributors, or during the installation of fuse inserts. The design allows for flexible mounting, both horizontally and vertically, reducing space requirements in the enclosure. Compatibility with phase busbar spacings of 185 mm makes it especially suitable for standard installation configurations.
Functions and Equipment in Detail
The switch is equipped with a bolted connection for the main current circuit, with cable entry from below. The operating element is positioned at the front, enabling easy operation. This is a version without fuse monitoring, without integrated or optional motor drive, and without function as an emergency stop device. Mounting is not for floor or front mounting, but designed for installation in enclosures with a busbar system. The connection type is thus oriented towards integration into existing switchgear.
Technology Explained Simply
The rated continuous current of 160 A means the switch can continuously carry this current value without thermal overload. The conditional rated short-circuit current of 120 kA describes the maximum short-circuit energy the switch can safely dissipate without damage. The IP30 degree of protection protects against contact with solid objects larger than 2.5 mm and against splashing water, making it suitable for indoor installations. The use of NH fuse inserts of size 00 enables modular and secure protection of the circuit.
Compatibility and Accessories
The switch disconnector can be combined with various accessories that extend its functionality. These include current transformers (CT) in various versions, such as 80/5A, 100/5A, 125/5A, 150/1A, 160/5A, which can be mounted on the rear. Additionally, auxiliary contacts (e.g. ZLBM auxiliary contact 1 NO) are available for signaling or control purposes. Prism terminals and single terminals (1.5–50 mm²) support secure cable connections. Cable covers for upper and lower cable exits, as well as spare parts such as covers for the front cover, are also available. The series is designed for use with busbars, enabling flexible integration into existing switchgear.
Mounting and Installation
Mounting is performed in enclosures with a busbar system, taking into account the phase spacing of 185 mm. The horizontal and vertical mounting options allow for space-saving installation. Cable entry is from below, supporting a clear structure within the enclosure. Operation is via the front-mounted operating element, ensuring safe and easy handling. Integration of current transformers and fuse inserts is tool-free, simplifying replacement and maintenance.
Operational Advantages
The switch disconnector offers high operational safety due to its tested construction in accordance with EN / IEC 60947-3. The modular design allows flexible expansion with accessories such as current transformers and auxiliary contacts. Simple mounting and maintenance reduce installation time and increase system availability. The use of NH fuse inserts ensures reliable circuit protection. The IP30 degree of protection ensures safe operation in indoor installations under normal operating conditions.